Notice of Violatlions (Current)
NOV Number:
E0020261258
(Pending)
Issue Date:
5/13/2026
Expiration Date:
7/12/2026
View NOV Form
| Tanks |
Violations |
| 1, 3 |
Dispensers - hoses cracked, split or worn and require replacement |
| 1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 7/8 sensor raised out of liquid. Remove liquid and lower sensor. It must be in contact with the bottom of the sump. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - All dispenser piping interstitial needs to be open. |
NOV Number:
E0020261259
(Pending)
Issue Date:
5/13/2026
Expiration Date:
7/12/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |