Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7037357
Status: Active
Facility Name: Hucks #371
Address: 1801 South 10th Street Mount Vernon, IL 62864
County: Jefferson
Property Parcel: 11-05-101-012
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000038
Green Tag Issue Date: 3/23/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Martin & Bayley, Inc.
Owner Address: P.O. Box 385 Carmi, IL 62821
Owner Status: Current Owner
Purchase Date: 1/15/2007
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 12/25/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/8/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0009763 Martin & Bayley, Inc. Current Owner 1/15/2007
U0019223 Paulin Transportation, Inc. Former Owner 5/10/1989

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251516 (Pending)    Issue Date: 6/11/2025    Expiration Date: 8/10/2025    View NOV Form

Tanks Violations
8 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Diesel west stp, cracks in lid.
Facility Miscellaneous - Emergency stop switch needs button. Located next too dispenser 5/6
6, 7 Miscellaneous - Tank interstitial sensor cap is broken on the riser.
4, 5, 6, 7, 8 Piping interstitial must be open in all sumps
5, 6, 7 Shear valve(s) not properly mounted and/or not at proper height. - Shear valve mounted against containment sump, not operational.
5, 6, 7 Submit Notification Form for Product Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank product change.
5, 6, 7 The Blended Fuel Compatibility Form for products greater than E10 and B20 has not been submitted as required. - Owners and operators are required to submit a Blended Fuel Compatibility Form 30 days prior to switching to a blended fuel product. The electronic form can be found at: https://webapps.sfm.illinois.gov/USTPortal/CompatibilityForm/Application.

NOV Number: E0020251517 (Pending)    Issue Date: 6/11/2025    Expiration Date: 8/10/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Sign located at dispenser 1/2 needs to be replaced.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
14-1355 3/10/2015 Removal Log 01162-2014REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/10/2015
OSFM First Notify Date: 8/5/1998 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 3/1/1989 Red Tag Issue Date:
Last Used Date: 3/9/2015 Fee Due: $0.00
Product Date: 5/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2012 11/7/2015
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2012 11/7/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/17/2014 10/17/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD
Overfill Prev Device Ball Float Vent Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/10/2015
OSFM First Notify Date: 8/5/1998 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 3/1/1989 Red Tag Issue Date:
Last Used Date: 3/9/2015 Fee Due: $0.00
Product Date: 5/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2012 11/7/2015
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2012 11/7/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/17/2014 10/17/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD
Overfill Prev Device Ball Float Vent Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/10/2015
OSFM First Notify Date: 8/5/1998 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 3/1/1989 Red Tag Issue Date:
Last Used Date: 3/9/2015 Fee Due: $0.00
Product Date: 5/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 11/7/2012 11/7/2015
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/7/2012 11/7/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/17/2014 10/17/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300i with CSLD
Overfill Prev Device Ball Float Vent Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 2000 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/5/1998 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 3/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 11/9/2022 11/9/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/5/2024 9/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/5/2024 9/5/2025
Overfill Prev Device Overfill Drop Tube Valve 9/5/2024 9/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech S175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown
Leak Detect - Piping Sump Sensor 9/5/2024 9/5/2025
Spill Contain Device Double Wall Spill Bucket 9/5/2024 9/5/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 9/23/2022
Piping Flexible Double Wall A.P.T. Poly Tech S175SC Precision Test (Piping) Pass 9/5/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 8/6/2019



Tank Number 5

Capacity: 15000 Petroleum Use:
Product: E15 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 10/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/5/2024 9/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/5/2024 9/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/5/2024 9/5/2025
Overfill Prev Device Overfill Drop Tube Valve 9/5/2024 9/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping STP/Tanktop Sump containment FRP 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025
Piping Single Wall STP/Tanktop Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025
Spill Contain Device Double Wall Spill Bucket 9/5/2024 9/5/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/5/2024



Tank Number 6

Capacity: 5000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 10/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/5/2024 9/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/5/2024 9/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/5/2024 9/5/2025
Overfill Prev Device Overfill Drop Tube Valve 9/5/2024 9/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping STP/Tanktop Sump containment FRP 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025
Spill Contain Device Double Wall Spill Bucket 9/5/2024 9/5/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/5/2024



Tank Number 7

Capacity: 5000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/28/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 10/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/5/2024 9/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/5/2024 9/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/5/2024 9/5/2025
Overfill Prev Device Overfill Drop Tube Valve 9/5/2024 9/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping STP/Tanktop Sump containment FRP 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025
Spill Contain Device Double Wall Spill Bucket 9/5/2024 9/5/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/5/2024



Tank Number 8

Capacity: 5000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/16/2014 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 10/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/5/2024 9/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/5/2024 9/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/5/2024 9/5/2025
Overfill Prev Device Overfill Drop Tube Valve 9/5/2024 9/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping STP/Tanktop Sump containment FRP 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025
Piping Single Wall STP/Tanktop Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025
Spill Contain Device Double Wall Spill Bucket 9/5/2024 9/5/2027
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 9/5/2024



Tank Number 9

Capacity: 6000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 4/28/2015 Abandoned Material:
Current Age: 10 Abandoned Date:
Install Date: 10/16/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection
Leak Detect - Piping Sump Sensor
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors
Overfill Prev Device Overfill Drop Tube Valve
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping STP/Tanktop Sump containment FRP
Spill Contain Device Double Wall Spill Bucket
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025



Name\ID K-1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/5/2024 9/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/5/2024 9/5/2025

MFD Motorfuel Dispensing Forms

No Forms Found