Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7034213
Status: Active
Facility Name: TEJ 321, Inc.
Address: 11005 Highway 4 Ava, IL 62907
County: Jackson
Property Parcel: 02-25-101-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: BB00642
Green Tag Issue Date: 6/12/2026
Green Tag Expire Date: 12/31/2028
MFD Type: Self Service

Owner Details

Owner Name: TEJ 321, Inc.
Owner Address: 981 State Route 4 Willisville, IL 62997
Owner Status: Current Owner
Purchase Date: 8/31/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/17/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040507 TEJ 321, Inc. Current Owner 8/31/2021
U0032492 Fleetwoods General Stores, Inc. Former Owner 12/10/2004
U0024137 Hepp Frank Former Owner 10/11/1999
U0029541 Stephenson, Joey & Teresa Former Owner 10/1/1999

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00567-2026UPG Upgrade Approved / Amended 5/21/2026 5/21/2026 11/23/2026 Documents

Notice of Violations (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
N/A 5/10/2011 Removal Log 00384-2011REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/20/2008
OSFM First Notify Date: 7/7/1995 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 7/1/1986 Red Tag Issue Date:
Last Used Date: 3/18/2008 Fee Due: $0.00
Product Date: 7/1/1986

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating No passing test found No passing test found
Leak Detect - Piping Pressurized Line Leak Detection No passing test found No passing test found
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 No passing test found No passing test found
Overfill Prev Device Overfill Drop Tube Valve No passing test found No passing test found
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Spill Contain Device Manhole Field Constructed No passing test found No passing test found
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/7/1995 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 7/1/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1986

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 8/7/2025 8/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/10/2026 6/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 6/10/2026 6/10/2027
Overfill Prev Device Overfill Drop Tube Valve 8/7/2025 8/7/2028
Piping Fiberglass Single Wall Piping Western Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 8/7/2025 8/7/2028
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 8/7/2025
Piping Fiberglass Single Wall Piping Western Precision Test (Piping) Pass 6/10/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 3/10/2022



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/7/1995 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 7/1/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1986

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 8/7/2025 8/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/10/2026 6/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 6/10/2026 6/10/2027
Overfill Prev Device Overfill Drop Tube Valve 8/7/2025 8/7/2028
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 8/7/2025 8/7/2028
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 6/10/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 3/10/2022



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/10/2011
OSFM First Notify Date: 7/7/1995 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 7/1/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1986

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/15/2009 4/15/2012
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/15/2009 4/15/2012
Leak Detect - Piping Pressurized Line Leak Detection 4/15/2009 4/15/2010
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/15/2009 4/15/2010
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 No passing test found No passing test found
Overfill Prev Device Overfill Drop Tube Valve No passing test found No passing test found
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Fiberglass Single Wall Piping Ameron Not applicable Not applicable
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Spill Contain Device Manhole Field Constructed No passing test found No passing test found
Spill Contain Device Single Wall Spill Bucket No passing test found No passing test found
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

No Tests Listed




Tank Number 5

Capacity: 3000 Petroleum Use: None
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/7/1995 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 7/1/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1986

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 8/7/2025 8/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/10/2026 6/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 6/10/2026 6/10/2027
Overfill Prev Device Overfill Drop Tube Valve 8/7/2025 8/7/2028
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 8/7/2025 8/7/2028
Tank STIP3 Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 6/10/2026
Tank STIP3 Single Wall Precision Test (Tank) Pass 3/10/2022

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

No Forms Found