Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7032367
Status: Active
Facility Name: Shawnee Quick Mart #1
Address: 111 W. Shawnee Avenue Shawneetown, IL 62984
County: Gallatin
Property Parcel: 05-002-082-01
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003438
Green Tag Issue Date: 5/31/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Shawnee Quick Mart, Inc.
Owner Address: 111 W. Shawnee Ave. Shawneetown, IL 62984
Owner Status: Current Owner
Purchase Date: 9/23/2013
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 11/15/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/27/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037248 Shawnee Quick Mart, Inc. Current Owner 9/23/2013
U0031236 McAnulty, Inc. Former Owner 1/14/2003
U0021869 Rash, Inc. Former Owner 10/22/1993

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251875 (Pending)    Issue Date: 7/25/2025    Expiration Date: 9/23/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020251880 (Pending)    Issue Date: 7/25/2025    Expiration Date: 9/23/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Annual line precision and mechanical line leak detector functional test not completed.
1 Dispensers - hoses cracked, split or worn and require replacement - Gasoline whip hose cracked.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Employee on site does not have Class C certificate.
Facility Missing list of designated Class A/B & C Operators
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2 Tank monitor does not appear to function properly and requires maintenance. - Green Power, Amber Warning and Red Alarm lights not functional, repair/replace.
1, 2 Triennial spill prevention equipment testing not completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/25/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 10/27/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 6/12/2024 6/12/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/12/2024 6/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 6/12/2024 6/12/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/24/2022 6/24/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/24/2022 6/24/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 6/12/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 7/29/2019



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/25/1994 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 10/27/1993 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/12/2024 6/12/2027
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 6/12/2024 6/12/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/12/2024 6/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 6/12/2024 6/12/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 6/24/2022 6/24/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/24/2022 6/24/2025
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 6/12/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 7/29/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found