Notice of Violatlions (Current)
NOV Number:
E0020260310
(Pending)
Issue Date:
2/6/2026
Expiration Date:
4/7/2026
View NOV Form
| Tanks |
Violations |
| 3 |
Miscellaneous - Dispensers - the following hoses and metering equipment are actively leaking and require immediate replacement |
| 1, 2, 3 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. |
NOV Number:
E0020260311
(Pending)
Issue Date:
2/6/2026
Expiration Date:
4/7/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |