Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7024722
Status: Active
Facility Name: Bost Truck Service
Address: 1134 North 11th Street Murphysboro, IL 62966
County: Jackson
Property Parcel:
Facility Type: Trucking Company
Owner Type: Private
Green Tag Decal: Y000605
Green Tag Issue Date: 1/27/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Bost Truck Service
Owner Address: 1134 North 11th Street Murphysboro, IL 62966
Owner Status: Current Owner
Purchase Date: 1/1/1999
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/2/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 1/27/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0001823 Bost Truck Service Current Owner 1/1/1999

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252007 (Pending)    Issue Date: 8/8/2025    Expiration Date: 10/7/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Minimum 4A:60BC are not present at each island and at an emergency shutoff switch
Facility Miscellaneous - Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters.

NOV Number: E0020252008 (Pending)    Issue Date: 8/8/2025    Expiration Date: 10/7/2025    View NOV Form

Tanks Violations
4 Miscellaneous - If hoses are attached to a hoseretrieving mechanism, the listed emergency breakaway device shall be installed between the point of attachment of the hose-retrieving mechanism to the hose and the hose nozzle valve.
Facility Missing copies of current testing certificates for operator training - A/B Certificate is expired.
4 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Contractor failed to submit inspection to OSFM.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
96-1962 10/23/1996 Removal Log 1957-96

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
96-1962 Eligible 3/13/1997 4/1/1997 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/23/1996
OSFM First Notify Date: 3/28/1989 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1994 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1998
OSFM First Notify Date: 3/28/1989 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1998
OSFM First Notify Date: 3/28/1989 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/3/2000 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 10/2/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/2/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/2/2025 7/2/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 7/2/2025 7/2/2026
Overfill Prev Device Overfill Drop Tube Valve 3/3/2022 3/3/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 7/2/2025 7/2/2028
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test (Piping) Pass 7/2/2025

Dispenser Information



Name\ID Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found