Notice of Violatlions (Current)
NOV Number:
E0020260778
(Pending)
Issue Date:
3/24/2026
Expiration Date:
5/23/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 3, 4 |
Submit Notification Form for Product Change - Tank 3 is now Premium Gasoline, Tanks 4 is now Diesel. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
NOV Number:
E0020260780
(Pending)
Issue Date:
3/24/2026
Expiration Date:
5/23/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum Signage. Signs shall be provided that are clearly visible to all self-service customers. The signs shall be made of all-weather material and the lettering shall be not less than ? inch high. The top of the signs shall be mounted no higher than 10 feet above grade, or at a height approved by OSFM, and shall include the following wording, at a minimum:
1) "Warning";
2) "Stop Engine";
3) "No Smoking";
4) "Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in
progress";
5) "It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers". |
| Facility |
Miscellaneous - Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. |