Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tanks (1, 3 & 4) were taken out of service on 11/14/24, and are 44 years old. Per 175.810(e) single wall USTs must be removed, as they are now condemned.
Tank #2 was previously abandoned in place on 3/14/19. Per 175.840(e), it states "when a UST is allowed to be abandoned-in-place, the abandoned-in-place UST shall be removed when the condition for issuing the abandonment no longer exists. The reason for abandonment, was tank #4 was located in the same tank bed as tanks 1, 3 & 4. Therefore since these tanks have to be removed, tank #2 will have to be removed too.