Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0039940 |
Veera Ashvi, LLC |
Current Owner |
9/9/2020 |
| U0034528 |
Wright, Leslie & Beverly |
Former Owner |
12/7/2007 |
| U0008547 |
Knapp Oil Company, Inc. |
Former Owner |
1/1/1902 |
Permits (Unexpired)
Click for permit history
| Permit Number |
Type |
Status |
OSFM Receive Date |
Issue Date |
Expiration Date |
Documents |
| 01593-2025UPG |
Upgrade |
Extension Granted |
11/20/2025 |
11/25/2025 |
11/29/2026 |
Documents |
Notice of Violations (Current)
NOV Number:
E0020252869
(Referred to Legal)
Issue Date:
10/29/2025
Expiration Date:
12/28/2025
View NOV Form
| Tanks |
Violations |
| 5, 6 |
Failed to Empty the Tank to 1" or Less |
| 5, 6 |
Submit Notification Form For Tank Status Change - Tanks are out of service. The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change. |
IEMA Numbers Associated with the Facility
| IEMA Number |
Inspection Date |
Inspection Type |
Permit Number |
| 07-0579 |
5/29/2007 |
Removal Log |
00671-2007REM |
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 07-0579 |
Eligible |
5/15/2007
|
5/24/2007
|
$10,000
|
|
Tank Number 1
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/29/2007 |
|
OSFM
First Notify Date: |
5/6/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1966 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/29/2007 |
|
OSFM
First Notify Date: |
5/6/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1966 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/2/2007 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/29/2007 |
|
OSFM
First Notify Date: |
5/6/1986 |
|
Abandoned Material: |
|
| Current Age: |
41 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1966 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
5/2/2007 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
5/29/2007 |
|
OSFM
First Notify Date: |
5/6/1986 |
|
Abandoned Material: |
Inert material mixed with portland cement |
| Current Age: |
32 |
|
Abandoned Date: |
6/18/1998 |
| Install Date: |
|
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 5
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/18/2007 |
|
Abandoned Material: |
|
| Current Age: |
19 |
|
Abandoned Date: |
|
| Install Date: |
6/13/2007 |
|
Red Tag Issue Date: |
1/21/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/14/2007 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
5/5/2025 |
5/5/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/5/2025 |
5/5/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS - 4i |
5/5/2025 |
5/5/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/16/2025 |
12/16/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
12/12/2025 |
12/12/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/12/2025 |
12/12/2028 |
|
Tank
|
Fiberglass Single Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
5/5/2025
|
|
Tank
|
Fiberglass Single Wall XERXES
|
Precision Test (Tank)
|
Pass
|
10/5/2023
|
Tank Number 6
| Capacity: |
4000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
6/18/2007 |
|
Abandoned Material: |
|
| Current Age: |
19 |
|
Abandoned Date: |
|
| Install Date: |
6/13/2007 |
|
Red Tag Issue Date: |
1/21/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
6/14/2007 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
5/5/2025 |
5/5/2028 |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
5/5/2025 |
5/5/2028 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
5/5/2025 |
5/5/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS - 4i |
5/5/2025 |
5/5/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
12/16/2025 |
12/16/2028 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
12/12/2025 |
12/12/2028 |
|
Spill Contain Device
|
Double Wall Spill Bucket |
12/12/2025 |
12/12/2028 |
|
Tank
|
Fiberglass Single Wall XERXES |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
5/5/2025
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
InActive |
|
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
12/12/2025
|
12/12/2028
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
12/12/2025
|
12/12/2028
|
Name\ID 4/5
| Status: |
InActive |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
| Facility Number |
Name |
City |
Received Date |
Letter |
|
7021575
|
Pickup Mart
|
Karnak
|
11/21/2025
|
Letter
Form
|