Facility |
A/B operator retraining required as a result of issuance of the Notice of Violation |
Facility |
Facility Operation and Maintenance Plan not completed or available. |
Facility |
Missing copies of current testing certificates for operator training - No Class A/B or Class C certificates available. |
Facility |
Missing copy of emergency instructions or emergency procedures plan |
Facility |
Missing list of designated Class A/B & C Operators |
4, 5 |
Required monthly tank leak test records not available. - Tanks must pass leak test at least once every 30 days. "Low level error" is not acceptable. |
4 |
Submit Notification Form for Product Change - Tank is now gasoline.
The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank product change. |
4, 5 |
Tank monitor does not appear to function properly and requires maintenance. - Green Power and Amber Warning lights not functional. |
4, 5 |
Tank precision test required. - Test required due to violations. |