Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7015832
Status: Inactive
Facility Name: Anderson Brothers Oil Company
Address: 909 W. 9th Street Mount Carmel, IL 62863
County: Wabash
Property Parcel: 11-20-300-011
Facility Type: Commercial / Retail
Owner Type: Private
Green Tag Decal: S002038
Green Tag Issue Date: 8/22/2017
Green Tag Expiration Date: 12/31/2019

Owner Details

Owner Name: Rick Anderson
Owner Address: 15889 Friendsville Ave. Mount Carmel, IL 62863
Owner Status: Current Owner
Purchase Date: 8/25/2019
Type of Financial Responsibility:
Financial Responsibility Reporting Due Date:

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 8/22/2017 12/31/2019

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039595 Anderson, Rick Current Owner 8/25/2019
U0000619 L.E. Anderson Brothers Oil Company, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020250425 (Referred to Legal)    Issue Date: 2/20/2025    Expiration Date: 4/21/2025    View NOV Form

Tanks Violations
1, 3, 4 Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. Upon my inspection on 1/4/24, I took stick readings of each tank and tanks #1, 3 & 4 still had more than an inch of product. Tanks were red tagged on 2/28/19.
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1, 2, 3, 4 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Single walled tanks were taken out of service on 02/28/19, and are 43 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/8/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 4/8/1981 Red Tag Issue Date: 2/28/2019
Last Used Date: 2/28/2019 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank SIR and Prec Tightness Testing
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank SIR and Prec Tightness Testing Precision Test (Tank) Pass 7/13/2017



Tank Number 2

Capacity: 8000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/8/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 4/8/1981 Red Tag Issue Date: 2/28/2019
Last Used Date: 2/28/2019 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank SIR and Prec Tightness Testing
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank SIR and Prec Tightness Testing Precision Test (Tank) Pass 7/13/2017



Tank Number 3

Capacity: 8000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/8/1986 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 4/8/1981 Red Tag Issue Date: 2/28/2019
Last Used Date: 2/28/2019 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank SIR and Prec Tightness Testing
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank SIR and Prec Tightness Testing Precision Test (Tank) Pass 7/13/2017



Tank Number 4

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Condemned Tank CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/22/1989 Abandoned Material:
Current Age: 44 Abandoned Date:
Install Date: 4/8/1981 Red Tag Issue Date: 2/28/2019
Last Used Date: 2/28/2019 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Corrosion Prot - Tank Impressed Current Cathodic Protection 7/17/2017 7/17/2018
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank SIR and Prec Tightness Testing
Overfill Prev Device Overfill Drop Tube Valve
Piping Galvanized Steel Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank SIR and Prec Tightness Testing Precision Test (Tank) Pass 7/13/2017

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found