Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041656 |
DLU CStores LLC |
Current Owner |
5/5/2025 |
| U0040495 |
CK United, LLC |
Former Owner |
12/13/2021 |
| U0030949 |
Mac's Convenience Stores, LLC |
Former Owner |
4/29/2008 |
| U0002795 |
Emro Marketing Co |
Former Owner |
12/31/1967 |
| U0026552 |
Speedway, LLC |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020253054
(Referred to Legal)
Issue Date:
11/18/2025
Expiration Date:
1/17/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 3 |
Annual electronic line leak detector test not completed. - Expired testing |
| 1, 2, 3 |
Annual leak detection certification not completed (Required annually). - Expired testing |
| 1, 2, 3 |
Annual piping impressed current test not completed. - Expired testing |
| 1, 2, 3 |
Annual tank impressed current system test not completed. - Expired testing |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 08-0443 |
Eligible |
6/17/2008
|
7/17/2008
|
$10,000
|
|
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/18/1986 |
|
Abandoned Material: |
|
| Current Age: |
48 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1978 |
|
Red Tag Issue Date: |
2/20/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1978 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Impressed Current Cathodic Protection |
4/10/2024 |
4/10/2025 |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
4/10/2024 |
4/10/2025 |
|
Corrosion Prot - Tank
|
Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P |
12/19/2023 |
12/19/2028 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/10/2024 |
4/10/2025 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
4/10/2024 |
4/10/2025 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/10/2024 |
4/10/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/10/2024 |
4/10/2027 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
4/10/2024
|
|
Tank
|
Steel Single Wall
|
Precision Test (Tank)
|
Pass
|
12/20/2023
|
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Mid-grade |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/18/1986 |
|
Abandoned Material: |
|
| Current Age: |
48 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1978 |
|
Red Tag Issue Date: |
2/20/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1978 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Impressed Current Cathodic Protection |
4/10/2024 |
4/10/2025 |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
4/10/2024 |
4/10/2025 |
|
Corrosion Prot - Tank
|
Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P |
12/19/2023 |
12/19/2028 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
8/8/2024 |
8/8/2025 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
4/10/2024 |
4/10/2025 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/10/2024 |
4/10/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/10/2024 |
4/10/2027 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
8/8/2024
|
|
Tank
|
Steel Single Wall
|
Precision Test (Tank)
|
Pass
|
12/20/2023
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
4/18/1986 |
|
Abandoned Material: |
|
| Current Age: |
48 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1978 |
|
Red Tag Issue Date: |
2/20/2026 |
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1978 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Impressed Current Cathodic Protection |
4/10/2024 |
4/10/2025 |
|
Corrosion Prot - Piping
|
Isolation Boots Flex Connector |
Not applicable |
Not applicable |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Impressed Current Cathodic Protection |
4/10/2024 |
4/10/2025 |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
4/10/2024 |
4/10/2025 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD |
4/10/2024 |
4/10/2025 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/10/2024 |
4/10/2027 |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/10/2024 |
4/10/2027 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
4/10/2024
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found