Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7011747
Status: Active
Facility Name: Mitchellville Country Store
Address: 5850 Highway 145 South Harrisburg, IL 62946
County: Saline
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000953
Green Tag Issue Date: 8/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 2 James, LLC
Owner Address: 5850 Hwy 145 Harrisburg, IL 62946
Owner Status: Current Owner
Purchase Date: 8/1/2012
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/16/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036657 2 James, LLC Current Owner 8/1/2012
U0032920 People's National Bank Former Owner 11/1/2008
U0028595 Hathaway, Jeff Former Owner 3/3/1999
U0035188 Kuhl-Fox, LLC Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00300-2025UPG Upgrade Approved / Issued 3/6/2025 3/13/2025 9/15/2025 Documents
01084-2025UPG Upgrade Approved / Issued 8/19/2025 8/19/2025 2/19/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251992 (Pending)    Issue Date: 8/7/2025    Expiration Date: 10/6/2025    View NOV Form

Tanks Violations
8 Line leak detection equipment in alarm or failed test, must repair or replace. - Diesel STP West Sensor in alarm, water in sump.
Facility Missing copies of current testing certificates for operator training - No Class C Operators at an attended facility.
Facility Missing list of designated Class A/B & C Operators
8 Piping interstitial must be open in all sumps
5, 6, 7 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves too low and not properly mounted, missing mounting bolts.
8 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
8 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Diesel STP sumps.
5, 7 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
991645 7/9/1999 Removal Log 01944-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-0694 Eligible 8/12/1999 8/25/1999 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 3000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/9/1999
OSFM First Notify Date: 5/1/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 6/30/2003 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 1120 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/9/1999
OSFM First Notify Date: 5/1/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1986 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/9/1999
OSFM First Notify Date: 5/1/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1986 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 1000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 7/9/1999
OSFM First Notify Date: 4/16/1999 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1986 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/6/2001 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/25/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/25/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/26/2025 6/26/2028
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 400 6/26/2025 6/26/2026
Overfill Prev Device Overfill Drop Tube Valve 6/12/2024 6/12/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/21/2023 4/21/2026
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/26/2025



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/6/2001 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/25/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/25/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/26/2025 6/26/2028
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 400 6/26/2025 6/26/2026
Overfill Prev Device Overfill Drop Tube Valve 6/12/2024 6/12/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/21/2023 4/21/2026
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/26/2025



Tank Number 7

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/6/2001 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 9/25/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/25/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/26/2025 6/26/2028
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 400 6/26/2025 6/26/2026
Overfill Prev Device Overfill Drop Tube Valve 6/12/2024 6/12/2027
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/21/2023 4/21/2026
Tank Composite Single Wall ACT 100 N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/26/2025



Tank Number 8

Capacity: 30000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/1/2013 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 3/7/2013 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/8/2013

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 400 6/26/2025 6/26/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 6/26/2025 6/26/2026
Overfill Prev Device Overfill Drop Tube Valve 6/12/2024 6/12/2027
Piping Flexible Double Wall A.P.T. Poly Tech P200SC N/A N/A
Piping Single Wall STP/Tanktop Sump 6/12/2024 6/12/2027
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 6/19/2020 6/19/2021
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026
Piping Single Wall STP/Tanktop Sump 6/12/2024 6/12/2027
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 6/11/2020 6/11/2021
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026
Spill Contain Device Single Wall Spill Bucket 6/12/2024 6/12/2027
Spill Contain Device Single Wall Spill Bucket 6/12/2024 6/12/2027
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 6/26/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/12/2024 6/12/2027
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 10 Satellite

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/12/2024 6/12/2027
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 6S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/12/2024 6/12/2027
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/12/2024 6/12/2027
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 9

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/12/2024 6/12/2027
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026

MFD Motorfuel Dispensing Forms

No Forms Found