Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0038480 |
Vinayaka, Inc. |
Current Owner |
9/1/2016 |
| U0004025 |
Dersch Energies, Inc. |
Former Owner |
11/1/1980 |
Notice of Violations (Current)
NOV Number:
E0020261633
(Pending)
Issue Date:
6/25/2026
Expiration Date:
8/24/2026
View NOV Form
| Tanks |
Violations |
| 3 |
Dispensers - hose breakaways are missing or leaking - Leaking swivel/Novel connection |
| Facility |
Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
| 1, 2, 3 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Transition sump install alarm |
| 1, 2, 3 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Testing Expired 4/27/2026 |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - All Sumps Transition, UDC,STP |
| 1, 2, 3 |
Tank sacrificial anode system not tested (Required every 3 years). - Testing Expired 2/15/2026 |
| 1, 2, 3 |
Triennial spill prevention equipment testing not completed. - Testing Expired 4/27/2026 |
| 1, 2, 3 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Testing Expired 4/20/2026 |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 07-0771 |
Eligible |
9/12/2007
|
9/25/2007
|
$10,000
|
|
| 20070771 |
Eligible |
6/24/2026
|
6/26/2026
|
$10,000
|
Letter
|
Tank Number 1
| Capacity: |
10152 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
46 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1980 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1980 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
2/15/2023 |
2/15/2026 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
8/21/2025 |
8/21/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/21/2025 |
8/21/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/27/2023 |
4/27/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/20/2023 |
4/20/2026 |
Leak Detect - Piping
|
Sump Sensor |
4/20/2023 |
4/20/2026 |
|
Piping
|
Single Wall Transition Sump |
4/20/2023 |
4/20/2026 |
Leak Detect - Piping
|
Sump Sensor |
4/20/2023 |
4/20/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/27/2023 |
4/27/2026 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
8/21/2025
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 2
| Capacity: |
10152 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
46 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1980 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1980 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
2/15/2023 |
2/15/2026 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
8/21/2025 |
8/21/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/21/2025 |
8/21/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/27/2023 |
4/27/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/20/2023 |
4/20/2026 |
Leak Detect - Piping
|
Sump Sensor |
4/20/2023 |
4/20/2026 |
|
Piping
|
Single Wall Transition Sump |
4/20/2023 |
4/20/2026 |
Leak Detect - Piping
|
Sump Sensor |
4/20/2023 |
4/20/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/27/2023 |
4/27/2026 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
8/21/2025
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 3
| Capacity: |
10152 |
|
Petroleum Use: |
|
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
46 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1980 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1980 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
STIP3 Cathodic Protection with Dielectric Coating |
2/15/2023 |
2/15/2026 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
8/21/2025 |
8/21/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 |
8/21/2025 |
8/21/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/27/2023 |
4/27/2026 |
|
Piping
|
Flexible Double Wall |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
4/20/2023 |
4/20/2026 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
4/20/2023 |
4/20/2026 |
|
Piping
|
Single Wall Transition Sump |
4/20/2023 |
4/20/2026 |
Leak Detect - Piping
|
Sump Sensor |
4/20/2023 |
4/20/2026 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
4/27/2023 |
4/27/2026 |
|
Tank
|
STIP3 Single Wall |
Not applicable |
Not applicable |
|
Vent, Riser, Fill Piping
|
Steel risers |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall
|
Precision Test (Piping)
|
Pass
|
8/21/2025
|
|
Tank
|
STIP3 Single Wall
|
Precision Test (Tank)
|
Pass
|
8/29/2024
|
Tank Number 4
| Capacity: |
560 |
|
Petroleum Use: |
Consumptive Use on Premises for Heating |
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Out of service |
|
CAS Code: |
|
| Regulated Status: |
State |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/3/1986 |
|
Abandoned Material: |
|
| Current Age: |
45 |
|
Abandoned Date: |
|
| Install Date: |
11/1/1980 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
10/1/1995 |
|
Fee Due: |
$0.00 |
| Product Date: |
11/1/1980 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
4/20/2023
|
4/20/2026
|
Leak Detect - Piping
|
Sump Sensor |
8/21/2025
|
8/21/2026
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
4/20/2023
|
4/20/2026
|
Leak Detect - Piping
|
Sump Sensor |
8/21/2025
|
8/21/2026
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
4/20/2023
|
4/20/2026
|
Leak Detect - Piping
|
Sump Sensor |
8/21/2025
|
8/21/2026
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
4/20/2023
|
4/20/2026
|
Leak Detect - Piping
|
Sump Sensor |
8/21/2025
|
8/21/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD