Notice of Violatlions (Current)
NOV Number:
E0020251799
(Pending)
Issue Date:
7/16/2025
Expiration Date:
9/14/2025
View NOV Form
Tanks |
Violations |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
Facility |
Miscellaneous - Emergency stops shall be interconnected so that activation of one emergency stop activates all the emergency stops whenever more than one emergency stop is provided. |
NOV Number:
E0020251800
(Pending)
Issue Date:
7/16/2025
Expiration Date:
9/14/2025
View NOV Form
Tanks |
Violations |
Facility |
Facility Operation and Maintenance Plan not updated to new requirements. - Template left on site. |
Facility |
Missing list of designated Class A/B & C Operators - Template left on site. |
5, 12, 13 |
Monthly line interstitial sensor records not available. - Monthly liquid status must be printed and saved for 2 years. Records not available. |
5, 12, 13 |
Piping interstitial must be open in all sumps - Plugs and jumper tubes must be removed from piping secondary in dispenser sumps. |
5, 10, 11, 12, 13 |
Required monthly tank interstitial sensor records not available. - Monthly liquid status must be printed and saved for 2 years. Records not available. |
11, 12 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |