Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6047208
Status: Active
Facility Name: Speedway #7269
Address: 5401 State Route 111 Pontoon Beach, IL 62040
County: Madison
Property Parcel: 18-2-14-26-00-000-30
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000189
Green Tag Issue Date: 11/27/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500 Springfield, OH 45501
Owner Status: Current Owner
Purchase Date: 7/9/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/27/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner 7/9/2018

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

No Notice of Violations Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/17/2021 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/13/2024 8/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/13/2024 8/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 9/29/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/29/2021



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/17/2021 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/13/2024 8/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/13/2024 8/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 10/2/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/29/2021



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 30000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/17/2021 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/13/2024 8/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/13/2024 8/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 9/29/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/29/2021



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/17/2021 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/13/2024 8/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/13/2024 8/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 9/29/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/29/2021



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/17/2021 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/13/2024 8/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/13/2024 8/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 9/29/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/29/2021



Tank Number 7

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/17/2021 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/19/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/13/2024 8/13/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 8/13/2024 8/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/13/2024 8/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/13/2024 8/13/2027
Piping Flexible Double Wall Franklin Fueling Systems UPP N/A N/A
Piping Single Wall STP/Tanktop Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025
Spill Contain Device Single Wall Spill Bucket 7/9/2024 7/9/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Franklin Fueling Systems UPP Precision Test (Piping) Pass 9/29/2021
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/29/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 21

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 21S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 23

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/9/2024 7/9/2027
Leak Detect - Piping Sump Sensor with positive shutdown 8/13/2024 8/13/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
6047208 Speedway #7269 Pontoon Beach 09/14/2021 Letter Form