Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6045206
Status: Active
Facility Name: HSHS St. Joseph's Hospital
Address: 12866 Troxler Ave. Highland, IL 62249
County: Madison
Property Parcel: 02-1-18-33-00-000-001
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: AA03994
Green Tag Issue Date: 2/27/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: HSHS St. Joseph's Hospital
Owner Address: 12866 Troxler Ave. Highland, IL 62249
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/13/2026

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036630 HSHS St. Joseph's Hospital Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251346 (Referred to Legal)    Issue Date: 5/23/2025    Expiration Date: 7/22/2025    View NOV Form

Tanks Violations
2 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Line interstitial sensor functional test not accomplished (Required annually).
1 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2500 Petroleum Use: Consumptive Use on Premises for Heating
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: State Removed Date:
OSFM First Notify Date: 6/26/2013 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 10/10/2012 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/10/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/7/2024 5/7/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/1/2025 8/1/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/1/2025 8/1/2026
Overfill Prev Device Overfill Alarm 8/1/2025 8/1/2028
Overfill Prev Device Overfill Drop Tube Valve 8/1/2025 8/1/2028
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 7/11/2025 7/11/2028
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 11/12/2019 11/12/2020
Leak Detect - Piping Sump Sensor 8/1/2025 8/1/2026
Spill Contain Device Single Wall Spill Bucket 8/1/2025 8/1/2028
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 8/1/2025



Tank Number 2

Capacity: 6000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/26/2013 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 10/10/2012 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/10/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/1/2025 8/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus 8/1/2025 8/1/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 8/1/2025 8/1/2026
Overfill Prev Device Overfill Alarm 8/1/2025 8/1/2028
Overfill Prev Device Overfill Drop Tube Valve 5/31/2022 5/31/2025
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 7/11/2025 7/11/2028
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 11/12/2019 11/12/2020
Leak Detect - Piping Sump Sensor 8/1/2025 8/1/2026
Piping Single Wall Transition Sump 7/11/2025 7/11/2028
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 11/12/2019 11/12/2020
Leak Detect - Piping Sump Sensor 8/1/2025 8/1/2026
Spill Contain Device Single Wall Spill Bucket 8/1/2025 8/1/2028
Tank Composite Double Wall Modern Welding Glasteel II N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test (Piping) Pass 8/1/2025

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found