Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6035108
Status: Active
Facility Name: Messer, LLC - Hartford ASU
Address: 1200 S. Delmar Avenue Hartford, IL 62048
County: Madison
Property Parcel:
Facility Type: Construction
Owner Type: Private
Green Tag Decal: Z003886
Green Tag Issue Date: 7/10/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Fleet

Owner Details

Owner Name: Messer, LLC
Owner Address: 200 Somerset Corporate Blvd. Suite 7000 Bridgewater, NJ 08807
Owner Status: Current Owner
Purchase Date: 4/2/2009
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/6/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039480 Messer, LLC Current Owner 4/2/2009
U0035091 Linde, Inc. Former Owner 6/15/1996
U0024935 B.O.C. Gases Former Owner 6/15/1996

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261196 (Pending)    Issue Date: 5/6/2026    Expiration Date: 7/5/2026    View NOV Form

Tanks Violations
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - STP and Dispenser sump anodes are past due testing.
1 Tank interstitial sensors in alarm or failed test, must repair or replace.
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP sump is past due testing.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code: 68476-30-2
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/20/1997 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 9/12/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/13/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/8/2022 9/8/2025
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/8/2022 9/8/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/1/2026 4/1/2027
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC 4/1/2026 4/1/2027
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/1/2026 4/1/2027
Overfill Prev Device Overfill Drop Tube Valve 12/6/2024 12/6/2027
Piping Fiberglass Double Wall N/A N/A
Piping Flex Connector Steel N/A N/A
Piping STP/Tanktop Sump containment FRP 9/8/2022 9/8/2025
Leak Detect - Piping Sump Sensor with positive shutdown
Leak Detect - Piping Sump Sensor 9/26/2023 9/26/2024
Leak Detect - Piping Sump Sensor 4/1/2026 4/1/2027
Spill Contain Device Single Wall Spill Bucket 12/6/2024 12/6/2027
Tank Fiberglass Double Wall Owens Corning N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 4/1/2026
Tank Fiberglass Double Wall Owens Corning Precision Test (Tank) Pass 9/30/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found