Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6032264
Status: Active
Facility Name: Benham BP, Inc.
Address: 3425 Missouri Avenue (Old Hwy 3) Granite City, IL 62040
County: Madison
Property Parcel: 17-1-20-06-00-000-017.001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000106
Green Tag Issue Date: 1/31/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Stephanie Benham
Owner Address: 2345 Emery Avenue Granite City, IL 62040
Owner Status: Current Owner
Purchase Date: 9/17/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/20/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/31/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040462 Benham, Stephanie Current Owner 9/17/2021
U0021762 Williams, Herman Former Owner 9/21/1993

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251934 (Pending)    Issue Date: 8/1/2025    Expiration Date: 9/30/2025    View NOV Form

Tanks Violations
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
3, 4, 5 Line interstitial sensors have been raised and rendered inoperational. - Dispenser 7/8 and 9/10 have raised sensors. The sensors must be at the lowest part of the sump.
3, 4, 5 Tank monitor does not appear to function properly and requires maintenance. - Printer is not working.
3, 4, 5 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispensers 7/8 and 9/10 contain water.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2021-1131 3/3/2022 Removal Log 00072-2022REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20211131 Eligible 12/19/2022 12/19/2022 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/3/2022
OSFM First Notify Date: 2/17/1994 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 9/21/1993 Red Tag Issue Date:
Last Used Date: 8/15/2013 Fee Due: $0.00
Product Date: 10/20/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/13/2012 1/13/2013
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Overfill Prev Device Ball Float Vent Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/3/2022
OSFM First Notify Date: 4/15/1997 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 9/21/1993 Red Tag Issue Date:
Last Used Date: 8/15/2013 Fee Due: $0.00
Product Date: 10/20/1993

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/13/2012 1/13/2013
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Overfill Prev Device Ball Float Vent Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/13/2023 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 5/12/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/20/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/30/2024 12/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 12/30/2024 12/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/30/2024 12/30/2025
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025
Spill Contain Device Double Wall Spill Bucket 6/30/2022 6/30/2025
Tank Composite Double Wall Lannon N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/29/2022
Tank Composite Double Wall Lannon Precision Test (Tank) Pass 8/29/2022



Tank Number 4

Capacity: 5000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/13/2023 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 5/12/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/20/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/30/2024 12/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 12/30/2024 12/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/30/2024 12/30/2025
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025
Spill Contain Device Double Wall Spill Bucket 6/30/2022 6/30/2025
Tank Composite Double Wall Lannon N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/29/2022
Tank Composite Double Wall Lannon Precision Test (Tank) Pass 8/29/2022



Tank Number 5

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/13/2023 Abandoned Material:
Current Age: 2 Abandoned Date:
Install Date: 5/12/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/20/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/30/2024 12/30/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 12/30/2024 12/30/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/30/2024 12/30/2025
Overfill Prev Device Overfill Drop Tube Valve 9/12/2022 9/12/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025
Spill Contain Device Double Wall Spill Bucket 6/30/2022 6/30/2025
Tank Composite Double Wall Lannon N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/29/2022
Tank Composite Double Wall Lannon Precision Test (Tank) Pass 8/29/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/30/2022 6/30/2025
Leak Detect - Piping Sump Sensor with positive shutdown 12/30/2024 12/30/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter