Notice of Violatlions (Current)
NOV Number:
E0020260755
(Pending)
Issue Date:
3/23/2026
Expiration Date:
5/22/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Water in Tank #1 Reg. STP Sump. |
NOV Number:
E0020260802
(Pending)
Issue Date:
3/26/2026
Expiration Date:
5/25/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Line interstitial sensor functional test not accomplished (Required annually). |
| 1, 2 |
Monthly line interstitial sensor records not available. |
| 1, 2 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - UDC needs tested or testing needs to be submitted. |
| 1, 2 |
Verify and test piping sump sensor for positive shutdown |