Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6024735
Status: Active
Facility Name: Little Nashville Truck Stop, LLC d/b/a Little Nashville BP
Address: 11724 State Rt. 127 Nashville, IL 62263
County: Washington
Property Parcel: 02-13-06-100-007
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001120
Green Tag Issue Date: 1/28/2025
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Waif Rackley Land Investment, LLC
Owner Address: P.O. Box 100 West Alton, MO 63386
Owner Status: Current Owner
Purchase Date: 3/22/2017
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 8/25/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038772 Waif Rackley Land Investment, LLC Current Owner 3/22/2017
U0035201 Mac Dales, Ltd. Former Owner 1/2/2009
U0003121 Clinton County Oil Company, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261087 (Pending)    Issue Date: 4/22/2026    Expiration Date: 6/21/2026    View NOV Form

Tanks Violations
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement - Dispenser #6 hose, Dispenser #2,#3,#7,#8 whip hose.
1, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Water in UDC under dispenser 3/4 and 5/6.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/25/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/7/2025 2/7/2028
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 2/7/2025 2/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/27/2025 10/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300j 10/27/2025 10/27/2026
Overfill Prev Device Ball Float Vent Valve OPW 53 10/9/2023 10/9/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/9/2023 10/9/2026
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 10/27/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/25/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/7/2025 2/7/2028
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 2/7/2025 2/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/27/2025 10/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300j 10/27/2025 10/27/2026
Overfill Prev Device Ball Float Vent Valve OPW 53 10/9/2023 10/9/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/9/2023 10/9/2026
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 10/27/2025



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/25/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/7/2025 2/7/2028
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/7/2025 2/7/2028
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 2/7/2025 2/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/27/2025 10/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300j 10/27/2025 10/27/2026
Overfill Prev Device Ball Float Vent Valve OPW 53 10/9/2023 10/9/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Double Wall Spill Bucket 10/16/2023 10/16/2026
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 10/27/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 8/14/2025



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/1988 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 10/25/1988 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/7/2025 2/7/2028
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 2/7/2025 2/7/2028
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/27/2025 10/27/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300j 10/27/2025 10/27/2026
Overfill Prev Device Overfill Drop Tube Valve 10/9/2023 10/9/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/9/2023 10/9/2026
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 10/27/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID Diesel

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found