Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6013715
Status: Active
Facility Name: Phillips 66 Alton
Address: 1660 E. Broadway
Alton, IL 62002
County: Madison
Property Parcel: 23-2-07-13-12-201-007; 08
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000195
Green Tag Issue Date: 2/6/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Shree Hari Fuel, LLC
Owner Address: 1660 E. Broadway Avenue
Alton, IL 62002
Owner Status: Current Owner
Purchase Date: 11/8/2023
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 1/11/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/6/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041064 Shree Hari Fuel, LLC Current Owner 11/8/2023
U0040689 SMJ Fuel, LLC Former Owner 6/28/2022
U0039585 RS Land Development, LLC Former Owner 4/15/2021
U0036268 Alton BP, Inc. Former Owner 6/1/2010
U0033315 Midwest Fuel & Gas Former Owner 1/1/2004
U0028018 Fuel & Gruel Inc. Former Owner 8/8/1996
U0003117 Thomas Oil Company, Inc. Former Owner 2/1/1985

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251408 (Pending)    Issue Date: 6/3/2025    Expiration Date: 8/2/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Record not available at the time of visit.
6, 7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Sump lid for both regular and premium are cracked. They are also unable to be seated to the sump. Repair or relpace.
6, 7 Document that emergency shut-off (shear valves) are in proper working order - Record not available at the time of visit.
Facility Facility Operation and Maintenance Plan not completed or available. - Record not available at the time of visit.
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
Facility Missing copies of 30 day Walkthrough Inspection Report. - Record not available at the time of visit.
Facility Missing copies of current testing certificates for operator training - Record not available at the time of visit.
Facility Missing copy of emergency instructions or emergency procedures plan - Record not available at the time of visit.
Facility Missing list of designated Class A/B & C Operators - Record not available at the time of visit.
6, 7 Required monthly tank leak test records not available.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
94-0492 4/18/1994 Removal Log
94-0492 7/31/1996 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
94-0492 Eligible 4/19/1994 5/9/1994 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/31/1996
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/31/1996
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/31/1996
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/18/1994
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 32 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 550 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 4/18/1994
OSFM First Notify Date: 7/1/1992 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 3/1/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/8/1998 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 8/8/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/23/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/3/2023 10/3/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/17/2024 10/17/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 10/17/2024 10/17/2025
Overfill Prev Device Overfill Drop Tube Valve 9/6/2023 9/6/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 9/6/2023 9/6/2026
Tank Composite Single Wall ACT 100 N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/17/2024



Tank Number 7

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/8/1998 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 8/8/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/23/1996

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/3/2023 10/3/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 10/17/2024 10/17/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 10/17/2024 10/17/2025
Overfill Prev Device Overfill Drop Tube Valve 9/6/2023 9/6/2026
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 9/6/2023 9/6/2026
Tank Composite Single Wall ACT 100 N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/17/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found