Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6011121
Status: Active
Facility Name: Fairview Moto Mart
Address: 6114 North Illinois Fairview Heights, IL 62208
County: St. Clair
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000184
Green Tag Issue Date: 6/13/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Moto, Inc.
Owner Address: 721 W. Main Street Belleville, IL 62222
Owner Status: Current Owner
Purchase Date: 11/1/1967
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/13/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0010647 Moto, Inc. Current Owner 11/1/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251931 (Pending)    Issue Date: 8/1/2025    Expiration Date: 9/30/2025    View NOV Form

Tanks Violations
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Concrete surrounding the STP sump is deteriorating and must be replaced. The manhole cover is rusted away and has become thin enough that it no loner provides adequate support and must be replaced.
3 Open electrical conduit or junction boxes. - Open junction box in the STP sump.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-2412 Eligible 7/18/2002 8/7/2002 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/24/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 9/1/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/31/2022 10/31/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/31/2022 10/31/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/2/2024 10/2/2025
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 with SCALD 10/2/2024 10/2/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/24/1986 Abandoned Material:
Current Age: 57 Abandoned Date:
Install Date: 11/1/1967 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/31/2022 10/31/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 10/9/2024 10/9/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/2/2024 10/2/2025
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 with SCALD 10/2/2024 10/2/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/24/1986 Abandoned Material:
Current Age: 57 Abandoned Date:
Install Date: 11/1/1967 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/31/2022 10/31/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 10/9/2024 10/9/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/2/2024 10/2/2025
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 with SCALD 10/2/2024 10/2/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/24/1986 Abandoned Material:
Current Age: 58 Abandoned Date:
Install Date: 1/1/1967 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/31/2022 10/31/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 10/9/2024 10/9/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/2/2024 10/2/2025
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 with SCALD 10/2/2024 10/2/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/24/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 9/1/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/31/2022 10/31/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/31/2022 10/31/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/2/2024 10/2/2025
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 with SCALD 10/2/2024 10/2/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/24/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 9/1/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1982

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/31/2022 10/31/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 10/31/2022 10/31/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/2/2024 10/2/2025
Leak Detect - Tank Automatic Tank Gauging Incon TS 550 with SCALD 10/2/2024 10/2/2025
Overfill Prev Device Overfill Drop Tube Valve 12/11/2024 12/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/11/2024 12/11/2027
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms