Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 6010094
Status: Active
Facility Name: Fairmont 66
Address: 5404 Collinsville Road East St. Louis, IL 62201
County: St. Clair
Property Parcel: 02-03.0-100-032
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002017
Green Tag Issue Date: 10/3/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Shri Satya Said Baba, Inc.
Owner Address: 5404 Collinsville Road Fairmont City, IL 62201
Owner Status: Current Owner
Purchase Date: 6/7/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/16/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/3/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035018 Shri Satya Said Baba, Inc. Current Owner 6/7/2006
U0030861 Vividh Inc Former Owner 10/1/2001
U0027614 St. Louis Petroleum & Marketing Former Owner 4/1/1998
U0005268 Floyd Emert Agent Former Owner 12/31/1967
U0027972 St. Louis Petroleum & Marketing Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251722 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
5, 6 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Tank 5 & 6 STP sumps and dispenser 5/6 UDC are past due testing.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
14-0548 6/10/2014 Removal Log 00438-2014REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
14-0548 Eligible 6/16/2014 7/31/2014 $5,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/10/2014
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 54 Abandoned Date:
Install Date: 6/1/1960 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/1/1960

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 2/15/1990 2/15/1995
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/13/2013 11/13/2014
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/10/2014
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 54 Abandoned Date:
Install Date: 6/1/1960 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/1/1960

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 2/15/1990 2/15/1995
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/10/2014
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 54 Abandoned Date:
Install Date: 6/1/1960 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/1/1960

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 2/15/1990 2/15/1995
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/13/2013 11/13/2014
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 1000 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/30/2011
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 6/1/1984 Red Tag Issue Date:
Last Used Date: 12/21/2010 Fee Due: $0.00
Product Date: 6/1/1984

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 11/23/2010 11/23/2011
Corrosion Prot - Tank Impressed Current Cathodic Protection 11/23/2010 11/23/2011
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Monthly Inv Ctrl and Prec Tight Testing 1/1/2010 1/1/2011

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2014 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 6/13/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/13/2014

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/10/2025 7/10/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/10/2025 7/10/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/10/2025 7/10/2026
Overfill Prev Device Overfill Drop Tube Valve 8/14/2024 8/14/2027
Piping Flexible Double Wall A.P.T. Poly Tech S150SC N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 7/10/2025 7/10/2028
Leak Detect - Piping Non-Discriminating Sump Sensor 6/27/2019 6/27/2020
Leak Detect - Piping Sump Sensor with positive shutdown 7/10/2025 7/10/2026
Spill Contain Device Double Wall Spill Bucket 8/14/2024 8/14/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 7/10/2025
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Precision Test (Piping) Pass 7/10/2025
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test (Piping) Pass 7/10/2025
Piping Flexible Double Wall A.P.T. Poly Tech S150SC Precision Test (Piping) Pass 7/10/2025
Piping Steel Single Wall Piping Precision Test (Piping) Pass 7/10/2025
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 9/6/2024



Tank Number 6

Capacity: 5000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2014 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 6/13/2014 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/13/2014

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/10/2025 7/10/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/10/2025 7/10/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 7/10/2025 7/10/2026
Overfill Prev Device Overfill Drop Tube Valve 8/14/2024 8/14/2027
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech S150SC N/A N/A
Piping Fiberglass Single Wall Piping Ameron N/A N/A
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 7/10/2025 7/10/2028
Leak Detect - Piping Non-Discriminating Sump Sensor 7/9/2018 6/27/2019
Leak Detect - Piping Sump Sensor with positive shutdown 7/10/2025 7/10/2026
Spill Contain Device Double Wall Spill Bucket 8/14/2024 8/14/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 7/10/2025
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Precision Test (Piping) Pass 7/10/2025
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test (Piping) Pass 7/10/2025
Piping Flexible Double Wall A.P.T. Poly Tech S150SC Precision Test (Piping) Pass 7/10/2025
Piping Steel Single Wall Piping Precision Test (Piping) Pass 7/10/2025
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 3/3/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/14/2024 8/14/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/14/2024 8/14/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2025 7/10/2028
Leak Detect - Piping Sump Sensor with positive shutdown 7/10/2025 7/10/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/10/2025 7/10/2028
Leak Detect - Piping Sump Sensor with positive shutdown 7/10/2025 7/10/2026

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
6010094 Fairmont 66 East St. Louis 06/11/2024 Letter Form