Notice of Violatlions (Current)
NOV Number:
E0020261336
(Pending)
Issue Date:
5/20/2026
Expiration Date:
7/19/2026
View NOV Form
| Tanks |
Violations |
| 1 |
Spill prevention equipment device is in disrepair and requires replacement. |
| 1, 2 |
Tank monitor does not appear to function properly and requires maintenance. - Probe out for the premium tank showing on the ATG. Must repair or replace. Supected issue with the probe for the regular tank. ATG readings do not match stick readings for water. |
| 1, 2 |
Tank precision test required. - Both tanks require a precision test. The regular due to water intrusion nd the premium tank due to no leak detection. |