Notice of Violatlions (Current)
NOV Number:
E0020260740
(Pending)
Issue Date:
3/19/2026
Expiration Date:
5/18/2026
View NOV Form
| Tanks |
Violations |
| 1, 2, 4 |
Line interstitial sensors have been raised and rendered inoperational. - Sump sensor under dispenser 1/2 has been raised out of the sump. Sensors must be located at the lowet part of the sump. |
| 1, 2, 4 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
| 1, 2, 4 |
Triennial spill prevention equipment testing not completed. |
| 1, 2, 4 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All STP and dispenser sumps must be tested. |
NOV Number:
E0020260741
(Pending)
Issue Date:
3/19/2026
Expiration Date:
5/18/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Annual Fire Detection Test has not been performed |