Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 5040225
Status: Active
Facility Name: Mr. Fuel #1245
Address: 4 Corvette Drive Litchfield, IL 62056
County: Montgomery
Property Parcel: 10-32-354-007
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000620
Green Tag Issue Date: 9/6/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Pilot Travel Centers, LLC
Owner Address: 5508 Lonas Rd. Knoxville, TN 37909
Owner Status: Current Owner
Purchase Date: 11/18/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0011913 Pilot Travel Centers, LLC Current Owner 11/18/2019
U0010556 M & M Service Company Former Owner 3/15/2001
U0027595 M & M Service Company Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00951-2025UPG Upgrade Approved / Issued 7/23/2025 7/23/2025 1/23/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251715 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
1 Install or replace lockable fill pipe caps. - Cap located in spill bucket not sealing completely. (North Diesel)
6 Line interstitial sensors have been raised and rendered inoperational.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 day not completed for June 2025
1, 2, 4, 5, 6, 7 Piping interstitial must be open in all sumps - All sumps
1, 4, 5, 6, 7 Triennial spill prevention equipment testing not completed.

NOV Number: E0020251717 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Signs need replaced at Dispensers 9/10,11/12, and 13/14. Signs shall be posted in all-weather materials by each actuator (or at the dispenser if the actuator is an integral part of the dispenser) and the lettering shall be not less than ? inch high.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
N/A 9/20/2023 Abandonment Log 00931-2023ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20230753 Eligible 5/5/2024 5/16/2024 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/15/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/15/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/22/2025 7/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/22/2025 7/22/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 7/20/2023 7/20/2024
Overfill Prev Device Overfill Alarm 7/20/2022 7/20/2025
Piping Blending Sump 10/4/2023 10/4/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 10/17/2023 10/17/2026
Leak Detect - Piping Non-Discriminating Sump Sensor 7/20/2023 7/20/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Spill Contain Device Single Wall Spill Bucket 5/7/2022 10/17/2023
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Blending Sump Precision Test (Piping) Pass 6/11/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/22/2025
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 8/24/2023
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 12/6/2019
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 7/22/2025



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/15/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/15/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/22/2025 7/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/22/2025 7/22/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 7/20/2023 7/20/2024
Overfill Prev Device Overfill Alarm 7/20/2022 7/20/2025
Piping Blending Sump 10/4/2023 10/4/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 10/17/2023 10/17/2026
Leak Detect - Piping Non-Discriminating Sump Sensor 7/20/2023 7/20/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Spill Contain Device Double Wall Spill Bucket 4/10/2024 4/10/2027
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Blending Sump Precision Test (Piping) Pass 6/11/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/22/2025
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 8/24/2023
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 7/22/2025
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 12/6/2019
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 7/22/2025



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2001 Abandoned Material: Gravel
Current Age: 24 Abandoned Date: 9/20/2023
Install Date: 3/15/2001 Red Tag Issue Date:
Last Used Date: 11/1/2021 Fee Due: $0.00
Product Date: 3/15/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/20/2023 7/20/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/20/2023 7/20/2024
Overfill Prev Device Overfill Alarm 7/20/2022 7/20/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor 7/28/2021 7/28/2022
Spill Contain Device Single Wall Spill Bucket 5/7/2022 5/7/2025
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 9/16/2021
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 7/28/2021



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/15/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/15/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/22/2025 7/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/22/2025 7/22/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 7/20/2023 7/20/2024
Overfill Prev Device Overfill Alarm 7/20/2022 7/20/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 9/13/2022 9/13/2025
Leak Detect - Piping Non-Discriminating Sump Sensor 7/20/2023 7/20/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Spill Contain Device Single Wall Spill Bucket 5/7/2022 5/7/2025
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 7/22/2025
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 7/22/2025



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/3/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 3/15/2001 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/15/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/22/2025 7/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/22/2025 7/22/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 7/20/2023 7/20/2024
Overfill Prev Device Overfill Alarm 7/20/2022 7/20/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 9/13/2022 9/13/2025
Leak Detect - Piping Non-Discriminating Sump Sensor 7/20/2023 7/20/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Spill Contain Device Double Wall Spill Bucket 8/7/2025 8/7/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 7/22/2025
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 7/22/2025



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/7/2005 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/9/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/24/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/22/2025 7/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus 7/22/2025 7/22/2026
Leak Detect - Tank SIR and Prec Tightness Testing Warren Rogers Assoc. Petro Network S3 Version D 7/20/2023 7/20/2024
Overfill Prev Device Overfill Alarm 7/20/2022 7/20/2025
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 9/13/2022 9/13/2025
Leak Detect - Piping Non-Discriminating Sump Sensor 7/20/2023 7/20/2024
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Spill Contain Device Single Wall Spill Bucket 5/7/2022 5/7/2025
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 7/22/2025
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 7/22/2025



Tank Number 7

Capacity: 20000 Petroleum Use: None
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/13/2020 Abandoned Material:
Current Age: 5 Abandoned Date:
Install Date: 3/26/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping American with Sensors/No Test Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/22/2025 7/22/2026
Overfill Prev Device Overfill Drop Tube Valve 7/22/2025 7/22/2028
Piping Blending Sump 10/4/2023 10/4/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026
Spill Contain Device Double Wall Spill Bucket 5/7/2022 5/7/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping American with Annual Prec Line Testing Suction Functional Pass 4/16/2020
Leak Detect - Piping American with Sensors/No Test Suction Functional Pass 7/22/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 1/5/2023
Tank Composite Double Wall Precision Test (Tank) Pass 7/28/2021

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 15/16

Status: InActive
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/20/2023 7/20/2024



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/17/2023 10/17/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/17/2023 10/17/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 19

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/17/2023 10/17/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/17/2023 10/17/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 20 Sat.

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 10/17/2023 10/17/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/13/2022 9/13/2025
Leak Detect - Piping Sump Sensor with positive shutdown 7/22/2025 7/22/2026

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
5040225 Mr. Fuel #1245 Litchfield 04/15/2020 Letter Form