Notice of Violatlions (Current)
NOV Number:
E0020251715
(Pending)
Issue Date:
7/8/2025
Expiration Date:
9/6/2025
View NOV Form
Tanks |
Violations |
1 |
Install or replace lockable fill pipe caps. - Cap located in spill bucket not sealing completely. (North Diesel) |
6 |
Line interstitial sensors have been raised and rendered inoperational. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - 30 day not completed for June 2025 |
1, 2, 4, 5, 6, 7 |
Piping interstitial must be open in all sumps - All sumps |
1, 4, 5, 6, 7 |
Triennial spill prevention equipment testing not completed. |
NOV Number:
E0020251717
(Pending)
Issue Date:
7/8/2025
Expiration Date:
9/6/2025
View NOV Form
Tanks |
Violations |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Signs need replaced at Dispensers 9/10,11/12, and 13/14.
Signs shall be posted in all-weather materials by each actuator (or at the dispenser if the actuator is an integral part of the dispenser) and the lettering shall be not less than ? inch high. |