Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 5017315
Status: Inactive
Facility Name: Paul Food Mart, Inc.
Address: 413 Ohren Lane Litchfield, IL 62056
County: Montgomery
Property Parcel: 10-32-300-006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001776
Green Tag Issue Date: 7/29/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Royal S&P, LLC
Owner Address: 413 Ohren Lane Litchfield, IL 62056
Owner Status: Current Owner
Purchase Date: 3/8/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/19/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040879 Royal S&P, LLC Current Owner 3/8/2023
U0030949 Mac's Convenience Stores, LLC Former Owner 12/30/2020
U0030258 Kooshtard Property III, LLC Former Owner 6/21/2001
U0014083 Smith Oil Co Of Kankakee Former Owner 3/10/1997
U0023790 Amoco Oil Company Former Owner 4/2/1996
U0023835 Amoco Oil Company Former Owner 4/4/1995
U0014431 Amoco Oil Company Former Owner 12/31/1967
U0029441 Smith Oil of Kankakee Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260792 (Pending)    Issue Date: 3/24/2026    Expiration Date: 5/23/2026    View NOV Form

Tanks Violations
6, 7, 8 Annual electronic line leak detector test not completed. - Testing expired 10/3/2024
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
6, 7, 8 Annual leak detection certification not completed (Required annually). - Testing expired 8/7/2024
6, 7, 8 Failed to Empty the Tank to 1" or Less
6, 7, 8 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Testing expired 1/12/2025
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of written UST facility operation & maintenance plan
Facility Missing list of designated Class A/B & C Operators
6, 7, 8 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Testing expired 8/24/2024
6, 7, 8 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
6, 7, 8 Submit Notification Form For Tank Status Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change.
6, 7, 8 Triennial spill prevention equipment testing not completed. - Testing expired 8/24/2024
6 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Testing expired 2/23/2025
6 Verify and test piping sump sensor for positive shutdown - Testing expired 8/7/2024

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
96-0713 11/13/1996 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 550 Used Oil Removed Federal $0.00 11/13/1996 - REM
2 6000 Gasoline Removed Federal $0.00 11/13/1996 - REM
3 10000 Gasoline Removed Federal $0.00 11/13/1996 - REM
4 10000 Gasoline Removed Federal $0.00 11/13/1996 - REM
5 550 Heating Oil Removed State $0.00 11/13/1996 - REM
6 10000 Diesel Fuel Out of service Federal $0.00
7 10000 Gasoline - Premium Out of service Federal $0.00
8 12000 Gasoline - Regular Out of service Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found