Notice of Violatlions (Current)
NOV Number:
E0020252563
(Pending)
Issue Date:
9/29/2025
Expiration Date:
11/28/2025
View NOV Form
Tanks |
Violations |
3 |
Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Failed testing 6/3/2025. |
Facility |
Submit Notification Form for Facility Information Change - Change to attended self service only or have the fire alarm tested and passed in order to dispense fuel without an attedent on duty. If you are no longer an Unattended facility, Submitt a letter stating that you are not operating as and unattended facility. You may not dispense fuel without an attendant present unless you have a passed fire alrm inspection. |
3 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispenser 5/6. Fluids in dispenser containment. Sensor in in the fluid and does not appear to function. |