Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4043854
Status: Active
Facility Name: Bob Melton Truck Service, Inc.
Address: 102 Shaffer Drive Downs, IL 61736
County: McLean
Property Parcel: 29-04-256-003
Facility Type: Trucking Company
Owner Type: Private
Green Tag Decal: Extend
Green Tag Issue Date: 1/2/2025
Green Tag Expiration Date: 1/29/2025

Owner Details

Owner Name: Bob Melton Truck Service, Inc.
Owner Address: 102 Shaffer Drive Downs, IL 61736
Owner Status: Current Owner
Purchase Date: 2/1/2007
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 5/26/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 5/26/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034442 Bob Melton Truck Service, Inc. Current Owner 2/1/2007

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251707 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Past due for annual testing - Past due annual testing.

NOV Number: E0020251708 (Pending)    Issue Date: 7/8/2025    Expiration Date: 9/6/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - No Annual Emergency Stop inspection available.
1 Annual leak detection certification not completed (Required annually). - Expired 3/26/2025 and needs to be completed.
1 Annual leak detection certification not completed (Required annually). - Expired 3/26/2025 and to be completed.
Facility Due to a red tagged tank(s) at this facility, after 60 days from the issuance date of this NOV, in the absence of full compliance, all tanks shall be red tagged - Red tag was placed on tank #1 on 1/29/2025 with 56" of product and current product level is 3.5" on 7/8/2025.
Facility Facility Operation and Maintenance Plan not completed or available. - No Facility Operation and maintenance plan available.
Facility Financial responsibility must be reported yearly - Financial Responsibility needs to be current.
Facility Missing copies of 30 day Walkthrough Inspection Report. - No 30 day Walkthrough available.
Facility Missing copies of Annual Walkthrough Inspection Report. - No Annual Walkthrough report available.
Facility Missing copies of current testing certificates for operator training - No current certificatews available for operator training.
Facility Missing copy of emergency instructions or emergency procedures plan - No Emergency Plan available.
Facility Missing list of designated Class A/B & C Operators - No A/B operator list available.
1 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Expired 1/4/2025 and needs to be completed.
Facility Submit Notification Form For Ownership Address Change - Need new Ownership change form.
1 Triennial spill prevention equipment testing not completed. - Expired 1/4/2025 and needs to be completed.
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Expired 1/4/2025 and needs to be completed.
1 Verify and test piping sump sensor for positive shutdown - Expired 3/26/2025 and to be be completed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/12/2008 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 1/23/2008 Red Tag Issue Date: 1/29/2025
Last Used Date: Fee Due: $0.00
Product Date: 1/23/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/26/2024 3/26/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/26/2024 3/26/2025
Overfill Prev Device Overfill Alarm 1/4/2022 1/4/2025
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 1/4/2022 1/4/2025
Leak Detect - Piping Sump Sensor 3/26/2024 3/26/2025
Spill Contain Device Single Wall Spill Bucket 1/4/2022 1/4/2025
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test (Piping) Pass 3/26/2024

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found