3, 4 |
Line interstitial sensors have been raised and rendered inoperational. - Dispenser 17 Sat. and Diesel STP sump sensors raised out of liquid. Sensors must be placed on the bottom at the lowest point of containments. |
4, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
4, 5 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Diesel STP sumps and diesel dispenser 17 Sat. |
2 |
Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Premium STP sump full of water, install cathodic protection. |