Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4033928
Status: Active
Facility Name: GPM #1802
Address: 1201 N. Mattis Ave. Champaign, IL 62821
County: Champaign
Property Parcel: 41-20-03-477-009
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002594
Green Tag Issue Date: 3/14/2025
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: CP Tanks, LLC
Owner Address: 811 W. Springfield Ave., Ste 201 Champaign, IL 61820
Owner Status: Current Owner
Purchase Date: 1/12/2012
Type of Financial Responsibility: Surety Bond
Financial Responsibility Reporting Due Date: 4/29/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036381 CP Tanks, LLC Current Owner 1/12/2012
U0018266 Colonial Pantry, LTD Former Owner
U0018897 Colonial Pantry, LTD. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261153 (Pending)    Issue Date: 4/30/2026    Expiration Date: 6/29/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020261156 (Pending)    Issue Date: 4/30/2026    Expiration Date: 6/29/2026    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation and must be completed within 30 days. - Anthony Galle has to leave a copy of his A/B operator license on site.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3 Miscellaneous - Middle Islands.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3 Monthly line interstitial sensor records not available. - Only have 4 months out of last 14 months.
1, 2, 3 Precision tank test required.
1, 2, 3 Required monthly tank leak test records not available. - Only have 4 months out of last 14 months.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Tank monitor does not appear to function properly and requires maintenance. - Has multiple alarms on it.
1, 2, 3 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - T1 STP, UDC'S 1/2 and 7/8 has water in containment sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/28/1995 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 5/12/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/12/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/27/2026 1/27/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/27/2026 1/27/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/6/2025 3/6/2028
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/27/2025 2/27/2028
Leak Detect - Piping Sump Sensor 1/27/2026 1/27/2027
Spill Contain Device Double Wall Spill Bucket 3/6/2025 3/6/2028
Tank Composite Single Wall Glasteel N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/27/2025
Tank Composite Single Wall Glasteel Precision Test (Tank) Pass 8/25/2025



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/28/1995 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 5/12/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/12/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/27/2026 1/27/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/27/2026 1/27/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/6/2025 3/6/2028
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/27/2025 2/27/2028
Leak Detect - Piping Sump Sensor 1/27/2026 1/27/2027
Spill Contain Device Double Wall Spill Bucket 3/6/2025 3/6/2028
Tank Composite Single Wall Glasteel N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/27/2025
Tank Composite Single Wall Glasteel Precision Test (Tank) Pass 8/25/2025



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/28/1995 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 5/12/1995 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/12/1995

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/27/2026 1/27/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 1/27/2026 1/27/2027
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 3/6/2025 3/6/2028
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/27/2025 2/27/2028
Leak Detect - Piping Sump Sensor 1/27/2026 1/27/2027
Spill Contain Device Double Wall Spill Bucket 3/6/2025 3/6/2028
Tank Composite Single Wall Glasteel N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 2/27/2025
Tank Composite Single Wall Glasteel Precision Test (Tank) Pass 8/25/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found