Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4026137
Status: Active
Facility Name: Friendly and Fresh Food Express
Address: 121 South Gilbert Street
Danville, IL 61832
County: Vermilion
Property Parcel: 23083050090060
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003111
Green Tag Issue Date: 12/29/2022
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Shantam1, LLC
Owner Address: 121 S. Gilbert Street
Danville, IL 61832
Owner Status: Current Owner
Purchase Date: 2/25/2021
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 10/15/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040122 Shantam1, LLC Current Owner 2/25/2021
U0039226 Maa Umiyakrupa, Inc. Former Owner 5/30/2018
U0030949 Mac's Convenience Stores, LLC Former Owner 4/29/2008
U0004767 Emro Marketing Co Former Owner 1/7/1997
U0026552 Speedway, LLC Former Owner 8/27/1996
U0014732 Ashland Oil Inc (Sa) Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250392 (Pending)    Issue Date: 2/14/2025    Expiration Date: 4/15/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020250393 (Pending)    Issue Date: 2/14/2025    Expiration Date: 4/15/2025    View NOV Form

Tanks Violation
3 Line leak detection equipment in alarm or failed test, must repair or replace. - Q3 Periodic Line Fail.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
97-2302 Eligible 4/6/1998 4/17/1998 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/17/1990 Abandoned Material:
Current Age: 53 Abandoned Date:
Install Date: 12/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/4/2024 3/4/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2024 3/7/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/7/2024 3/7/2025
Overfill Prev Device Overfill Drop Tube Valve 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 3/7/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/17/1990 Abandoned Material:
Current Age: 53 Abandoned Date:
Install Date: 12/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/4/2024 3/4/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2024 3/7/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/7/2024 3/7/2025
Overfill Prev Device Overfill Drop Tube Valve 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 3/7/2024



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/17/1990 Abandoned Material:
Current Age: 53 Abandoned Date:
Install Date: 12/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 3/4/2024 3/4/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/7/2024 3/7/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 3/7/2024 3/7/2025
Overfill Prev Device Overfill Drop Tube Valve 3/7/2024 3/7/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 3/7/2024 3/7/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 3/7/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms