Notice of Violatlions (Current)
NOV Number:
E0020260839
(Pending)
Issue Date:
3/31/2026
Expiration Date:
5/30/2026
View NOV Form
| Tanks |
Violations |
| 4 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Tanknology failed due to RUL leak detector failed testing. The LD failed to catch a 3.0 gph simulated leak rate. |