Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4019390
Status: Active
Facility Name: United Parcel Service
Address: 2209 South 14th Street Mattoon, IL 61938
County: Coles
Property Parcel:
Facility Type: Trucking Company
Owner Type: Private
Green Tag Decal: AA00390
Green Tag Issue Date: 4/22/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: United Parcel Service
Owner Address: 2349 Hubbard Avenue Decatur, IL 62526
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/21/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 4/22/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0015403 United Parcel Service Current Owner
U0000837 Ash Realty Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00379-2025UPG Upgrade Approved / Issued 3/31/2025 3/31/2025 9/30/2025 Documents

Notice of Violatlions (Current)

NOV Number: E0020250152 (Pending)    Issue Date: 1/16/2025    Expiration Date: 3/17/2025    View NOV Form

Tanks Violations
4 Spill prevention equipment device is in disrepair and requires replacement. - OSFM received a Containment Sump Testing form from a licensed UST contractor on 9/27/24, declaring tank #4 failed the triennial testing on 9/18/24. Contractor states, "There are 2 small cracks found during the hydrostatic testing".

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
89-0862 8/4/1992 Removal Log
890862 6/18/1990 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/18/1990
OSFM First Notify Date: 4/1/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 6/1/1989 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 8/4/1992
OSFM First Notify Date: 4/1/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/4/1992
OSFM First Notify Date: 4/1/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/13/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 8/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/1/1990

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/18/2024 9/18/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/18/2024 9/18/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/18/2024 9/18/2025
Overfill Prev Device Overfill Drop Tube Valve 4/7/2025 4/7/2028
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 9/18/2024 9/18/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/18/2024 9/18/2025
Spill Contain Device Double Wall Spill Bucket 4/7/2025 4/7/2028
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 9/18/2024

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/18/2024 9/18/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/18/2024 9/18/2025



Name\ID 1/2

Status: Removed
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/18/2024 9/18/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/18/2024 9/18/2025



Name\ID 2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/18/2024 9/18/2027
Leak Detect - Piping Sump Sensor with positive shutdown 9/18/2024 9/18/2025

MFD Motorfuel Dispensing Forms

No Forms Found