Facility Number: 4017276
Status: Active
Facility Name: Philo South Mart, Inc. CK #4700094
Address: 1821 So. Philo Road Urbana, IL 61801
County: Champaign
Property Parcel: 93-21-21-126-009
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003142
Green Tag Issue Date: 4/13/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: CK United, LLC
Owner Address: 300 N. Martingale Rd. Suite 750 Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 12/13/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/31/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 2/1/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040495 CK United, LLC Current Owner 12/13/2021
U0030949 Mac's Convenience Stores, LLC Former Owner 12/30/2020
U0030252 Kooshtard Property II, LLC Former Owner 6/21/2001
U0023515 Johnson Oil Company, L.L.C. Former Owner 4/6/1995
U0023835 Amoco Oil Company Former Owner 4/4/1995
U0014431 Amoco Oil Company Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252122 (Pending)    Issue Date: 8/18/2025    Expiration Date: 10/17/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020252129 (Pending)    Issue Date: 8/18/2025    Expiration Date: 10/17/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
7, 8 Annual leak detection certification not completed (Required annually).
7, 8 Annual line precision and mechanical line leak detector functional test not completed.
Facility Financial responsibility must be reported yearly
Facility Miscellaneous - Emergency Switch Sign Is Missing. Each emergency stop shall be identified by a sign stating "EMERGENCY STOP" in 2 inch red capital letters.
Facility Missing copies of Annual Walkthrough Inspection Report.
7, 8 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
Facility Submit Notification Form for Facility Information Change - Snak Atak
Facility Submit Notification Form For Ownership Change - Black Night 24, LLC 902 Carnegie Center Blvd, Suite 520 Princeton, NJ 08540-0000
7, 8 Tank monitor does not appear to function properly and requires maintenance. - Lights out power and warning on tank monitor.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
950030 1/4/1995 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
92-3430 Eligible 2/21/1996 3/25/1996 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 550 Used Oil Removed Federal $0.00 01/04/1995 - REM
2 6000 Gasoline Removed Federal $0.00 01/04/1995 - REM
3 6000 Gasoline Removed Federal $0.00 01/04/1995 - REM
5 8000 Gasoline Removed Federal $0.00 01/04/1995 - REM
6 550 Heating Oil Removed State $0.00 01/04/1995 - REM
7 10000 Gasoline - Premium Currently in use Federal $0.00
8 12000 Gasoline - Regular Currently in use Federal $0.00
9 Removed Exempt 01/04/1995 - REM
10 Removed Exempt 01/18/1995 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms