Notice of Violatlions (Current)
NOV Number:
E0020260765
(Pending)
Issue Date:
3/24/2026
Expiration Date:
5/23/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
NOV Number:
E0020260766
(Pending)
Issue Date:
3/24/2026
Expiration Date:
5/23/2026
View NOV Form
| Tanks |
Violations |
| 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - Tank 2 shows normal sensor report with STP full of water. |
| 2 |
Line leak detection equipment in alarm or failed test, must repair or replace. - Tanknology failed due to PUL LD failed to meter a 3.0 gal leak |
| 1, 2, 3 |
Piping interstitial must be open in all sumps |
| 1, 2, 3 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - All STP'S and UDC'S because system has double wall piping which is to be open at interstitial on all piping. Must show documentation from licensed conctractor work preformed. |