Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4013154
Status: Active
Facility Name: Brake Time
Address: 203 Lombard Street Mahomet, IL 61853
County: Champaign
Property Parcel: 15-13-15-177-021
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003113
Green Tag Issue Date: 1/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Brake Time IL Properties, LLC
Owner Address: 6300 Richmond Avenue, Suite 300 Houston, TX 77057
Owner Status: Current Owner
Purchase Date: 11/14/2024
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/27/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041353 Brake Time IL Properties, LLC Current Owner 11/14/2024
U0039389 Minit Mart, LLC Former Owner 12/5/2018
U0026726 TA Operating, LLC Former Owner 6/8/2016
U0007457 Illico Incorporated Former Owner
U0009577 Illico Incorporated Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252232 (Pending)    Issue Date: 8/27/2025    Expiration Date: 10/26/2025    View NOV Form

Tanks Violations
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - James Hamilton from Tanknology for missing copy's of tank passing test with his 30 day walkthrough.
6, 7, 8 Line interstitial sensor functional test not accomplished (Required annually). - UDC 13/14.
6, 7, 8 Required monthly tank leak test records not available.
6, 7, 8 Triennial spill prevention equipment testing not completed. - UDC 3/4.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-1954 8/18/1999 Removal Log 02390-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-1954 Eligible 11/15/1999 12/2/1999 $10,000
99-0547 Eligible 11/15/1999 12/2/1999 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/13/1999
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 12/20/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/13/1999
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 12/20/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/13/1999
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 12/20/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 1000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 8/13/1999
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 12/20/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/13/1999
OSFM First Notify Date: 5/6/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 12/20/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 12/4/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/18/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/22/2025 4/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/22/2025 4/22/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 4/22/2025 4/22/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 4/22/2025 4/22/2028
Leak Detect - Piping Non-Discriminating Sump Sensor 6/14/2022 6/14/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026
Spill Contain Device Single Wall Spill Bucket 6/14/2022 6/14/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/20/2022
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 5/9/2024



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 12/4/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/18/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/22/2025 4/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/22/2025 4/22/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 4/22/2025 4/22/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 4/22/2025 4/22/2028
Leak Detect - Piping Non-Discriminating Sump Sensor 6/14/2022 6/14/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026
Spill Contain Device Single Wall Spill Bucket 6/14/2022 6/14/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/14/2022
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 5/9/2024



Tank Number 8

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/10/2001 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 12/4/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/18/2001

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/22/2025 4/22/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/22/2025 4/22/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 4/22/2025 4/22/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 4/22/2025 4/22/2028
Leak Detect - Piping Non-Discriminating Sump Sensor 6/14/2022 6/14/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026
Spill Contain Device Single Wall Spill Bucket 6/14/2022 6/14/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 6/14/2022
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 5/9/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 10/24/2025 10/24/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/1/2022 4/22/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/22/2025 4/22/2028
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2025 4/22/2026

MFD Motorfuel Dispensing Forms

No Forms Found