Facility Number: 4009648
Status: Active
Facility Name: Freedom Oil Company
Address: 1802 West Market Street Bloomington, IL 61701
County: McLean
Property Parcel: 21-05-152-002
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z002589
Green Tag Issue Date: 9/30/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Freedom Oil Company
Owner Address: 814 W. Chestnut St. Bloomington, IL 61702
Owner Status: Current Owner
Purchase Date: 5/1/2001
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0023261 Freedom Oil Company Current Owner 5/1/2001
U0000793 Arnold Owens, Inc. Former Owner 6/1/1989

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020260767 (Pending)    Issue Date: 3/24/2026    Expiration Date: 5/23/2026    View NOV Form

Tanks Violations
5, 6, 7 Annual electronic line leak detector test not completed. - Expired 1/9/2026 and needs to be completed.
5, 6, 7 Annual leak detection certification not completed (Required annually). - Annual Leak detection expired 1/9/2026 and needs to be completed.
6, 7 Line interstitial sensor functional test not accomplished (Required annually). - Expired 1/9/2026 and needs to be completed.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30 Day walthrough needs to be up to date.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough needs to be completed.
Facility Missing copies of current testing certificates for operator training - Certificates need to be updated.
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Expired and needs to be completed.
Facility Submit Notification Form For Ownership Change - New Ownership Change needs to be completed.
6, 7 Tank interstitial sensor functional test not accomplished (Required annually). - Expired 1/9/2026 and needs to be completed.
6, 7 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Tank containment sumps are full of water and needs to be removed and maintained dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
07-1370 11/6/2007 Removal Log 01708-2007REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
88-0952 Eligible 6/20/2003 7/16/2003 $15,000
07-1370 Eligible 1/20/2009 2/11/2009 $15,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 4000 Gasoline Removed Federal $0.00 11/06/2007 - REM
2 4000 Gasoline Removed Federal $0.00 11/06/2007 - REM
3 4000 Gasoline Removed Federal $0.00 11/06/2007 - REM
4 4000 Gasoline Removed Federal $0.00 11/06/2007 - REM
5 6000 Diesel Fuel Currently in use Federal $0.00
6 8000 Gasoline - Premium Currently in use Federal $0.00
7 12000 Gasoline - Regular Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active