Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4007062
Status: Active
Facility Name: Circle K #1313
Address: 205 1st Drive West Decatur, IL 62521
County: Macon
Property Parcel: 23-34-100-062-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000861
Green Tag Issue Date: 4/25/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Mac's Convenience Stores, LLC
Owner Address: 1100 Situs Court, Suite 100 Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 4/29/2008
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 1/26/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/25/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030949 Mac's Convenience Stores, LLC Current Owner 4/29/2008
U0016241 Emro Marketing Co Former Owner 12/31/1967
U0026552 Speedway, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251829 (Pending)    Issue Date: 7/21/2025    Expiration Date: 9/19/2025    View NOV Form

Tanks Violations
11 Line interstitial sensors have been raised and rendered inoperational. - Sensor has been raised in Tank #11 (REG) containment sump and needs to be lowered.
10, 11, 12 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispensers #1 and #2 have a raised sensor and containment is full of water. Remove water and repair containment.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2021-0213 12/8/2021 Removal Log 00880-2021REM
2021-0213 12/7/2021 Removal Log 00880-2021REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-0768 Eligible 7/1/1998 7/28/1998 $10,000
04-0899 Eligible 3/15/2005 3/30/2005 $10,000
04-1674 Eligible 3/15/2005 3/30/2005 $10,000
20210213 Eligible 7/26/2021 7/26/2021 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/1/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/1/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 8/1/1987
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/8/2021
OSFM First Notify Date: 8/21/1987 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1987 Red Tag Issue Date:
Last Used Date: 2/1/2021 Fee Due: $0.00
Product Date: 7/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/6/2021 7/6/2024
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/5/2021 3/5/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/3/2020 9/3/2021
Overfill Prev Device Overfill Drop Tube Valve 11/15/2018 11/15/2021
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 11/15/2018 11/15/2021
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/11/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/11/2021



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/8/2021
OSFM First Notify Date: 8/21/1987 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1987 Red Tag Issue Date:
Last Used Date: 2/1/2021 Fee Due: $0.00
Product Date: 7/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/6/2021 7/6/2024
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/3/2020 9/3/2021
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/3/2020 9/3/2021
Overfill Prev Device Overfill Drop Tube Valve 11/15/2018 11/15/2021
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 11/15/2018 11/15/2021
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/11/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/11/2021



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/7/2021
OSFM First Notify Date: 8/21/1987 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/6/2021 7/6/2024
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/5/2021 3/5/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/3/2020 9/3/2021
Overfill Prev Device Overfill Drop Tube Valve 11/15/2018 11/15/2021
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 11/15/2018 11/15/2021
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/11/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 8/4/2021



Tank Number 7

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/7/2021
OSFM First Notify Date: 8/21/1987 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/6/2021 7/6/2024
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/5/2021 3/5/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/3/2020 9/3/2021
Overfill Prev Device Overfill Drop Tube Valve 11/15/2018 11/15/2021
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 11/15/2018 11/15/2021
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 2/11/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/11/2021



Tank Number 8

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 12/7/2021
OSFM First Notify Date: 8/21/1987 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1987

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/6/2021 7/6/2024
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/25/2021 8/25/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 9/3/2020 9/3/2021
Overfill Prev Device Overfill Drop Tube Valve 11/15/2018 11/15/2021
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 11/15/2018 11/15/2021
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 8/25/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 2/11/2021



Tank Number 9

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/17/2022 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/16/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 2/5/2025 2/5/2026
Overfill Prev Device Overfill Drop Tube Valve 2/5/2025 2/5/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026
Spill Contain Device Double Wall Spill Bucket 2/5/2025 2/5/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/16/2022



Tank Number 10

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/17/2022 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/16/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 2/5/2025 2/5/2026
Overfill Prev Device Overfill Drop Tube Valve 2/5/2025 2/5/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026
Spill Contain Device Double Wall Spill Bucket 2/5/2025 2/5/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/16/2022



Tank Number 11

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/17/2022 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/16/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2025 2/5/2026
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 2/5/2025 2/5/2026
Overfill Prev Device Overfill Drop Tube Valve 2/5/2025 2/5/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026
Spill Contain Device Double Wall Spill Bucket 2/5/2025 2/5/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/16/2022



Tank Number 12

Capacity: 7000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/17/2022 Abandoned Material:
Current Age: 3 Abandoned Date:
Install Date: 12/16/2021 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 3/14/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 2/5/2025 2/5/2026
Overfill Prev Device Overfill Drop Tube Valve 2/5/2025 2/5/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026
Spill Contain Device Double Wall Spill Bucket 2/5/2025 2/5/2028
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 2/5/2025
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 3/16/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/6/2025 2/6/2028
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2025 2/5/2026

MFD Motorfuel Dispensing Forms

No Forms Found