Notice of Violatlions (Current)
NOV Number:
E0020251651
(Pending)
Issue Date:
7/1/2025
Expiration Date:
8/30/2025
View NOV Form
| Tanks |
Violations |
| 1, 3 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Missing ground cover handle on STP's |
| 1 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Replacing all ground covers and innner covers - delay on parts. |