Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3042761
Status: Active
Facility Name: Williamsfield Fast Stop
Address: 218 Illinois Route 1-80 Williamsfield, IL 61489
County: Knox
Property Parcel: 12-23-200-019
Facility Type: Unattended Self-Service Station
Owner Type: Private
Green Tag Decal: Z004018
Green Tag Issue Date: 9/6/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Unattended Self Service

Owner Details

Owner Name: West Central FS, Inc.
Owner Address: 1445 Monmouth Blvd. Galesburg, IL 61401
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/1/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030073 West Central FS, Inc. Current Owner
U0032679 Riverland F.S., Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261180 (Pending)    Issue Date: 5/6/2026    Expiration Date: 7/5/2026    View NOV Form

Tanks Violations
2, 3 Line interstitial sensors have been raised and rendered inoperational. - STP's
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
2 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 6/15/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2026 1/29/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2026 1/29/2027
Overfill Prev Device Overfill Drop Tube Valve 1/28/2025 1/28/2028
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Flexible Double Wall A.P.T. Poly Tech P200SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor 1/29/2026 1/29/2027
Spill Contain Device Single Wall Spill Bucket 1/28/2025 1/28/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test (Piping) Pass 1/29/2026
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 1/29/2026
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/28/2008



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 6/15/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2026 1/29/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2026 1/29/2027
Overfill Prev Device Overfill Drop Tube Valve 1/28/2025 1/28/2028
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor 1/29/2026 1/29/2027
Spill Contain Device Single Wall Spill Bucket 1/28/2025 1/28/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test (Piping) Pass 1/29/2026
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 1/28/2025
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/28/2008



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/2005 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 6/15/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/15/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 1/29/2026 1/29/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2026 1/29/2027
Overfill Prev Device Overfill Drop Tube Valve 1/28/2025 1/28/2028
Piping Flexible Double Wall A.P.T. Poly Tech P200SC N/A N/A
Piping Single Wall STP/Tanktop Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor 1/29/2026 1/29/2027
Spill Contain Device Single Wall Spill Bucket 1/28/2025 1/28/2028
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 1/29/2026
Piping Flexible Double Wall A.P.T. Poly Tech P200SC Precision Test (Piping) Pass 1/28/2025
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/28/2008

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2026 1/29/2027



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2026 1/29/2027



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor 1/28/2025 1/28/2026
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2026 1/29/2027



Name\ID DSL Sat.

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 1/28/2025 1/28/2028
Leak Detect - Piping Sump Sensor 1/28/2025 1/28/2026
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2026 1/29/2027

MFD Motorfuel Dispensing Forms

No Forms Found