5 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Transition Sump East lid must be removable to allow for inspection. |
1, 2, 3, 4 |
Dispensers - hoses cracked, split or worn and require replacement |
1, 2, 3, 4, 5 |
Piping interstitial must be open in all sumps - Dispensers 1/2, 3/4, 5/6, 7/8. |
2, 3, 4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Both East & West STP's |