Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3041115
Status: Active
Facility Name: Hy-Vee Gas
Address: 1602 Jackson Street Macomb, IL 61455
County: McDonough
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001483
Green Tag Issue Date: 8/22/2024
Green Tag Expire Date: 12/31/2026
MFD Type: N/A

Owner Details

Owner Name: Hy-Vee, Inc.
Owner Address: 5820 Westown Parkway West Des Moines, IA 50266
Owner Status: Current Owner
Purchase Date: 5/17/2002
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 9/29/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030721 Hy-Vee, Inc. Current Owner 5/17/2002

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261246 (Pending)    Issue Date: 5/12/2026    Expiration Date: 7/11/2026    View NOV Form

Tanks Violations
1, 2, 3 Annual electronic line leak detector test not completed. - Electronic Pressurized Line Leak Detection test Expired 10-14-2025.
1, 2, 3 Annual leak detection certification not completed (Required annually). - Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD test Expired 10-14-2025.
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Tank top lid rim is bent in, making the STP inaccessible.
1, 2, 3 Line interstitial sensor functional test not accomplished (Required annually). - Sump Sensors test Expired 10-14-2025.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/24/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 7/31/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/31/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/31/2025 7/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 7/31/2025 7/31/2026
Overfill Prev Device Overfill Drop Tube Valve 7/31/2025 7/31/2028
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/19/2023 10/19/2026
Leak Detect - Piping Sump Sensor 7/31/2025 7/31/2026
Spill Contain Device Single Wall Spill Bucket 10/19/2023 10/19/2026
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 15000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/24/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 7/31/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/31/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/31/2025 7/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 7/31/2025 7/31/2026
Overfill Prev Device Overfill Drop Tube Valve 7/31/2025 7/31/2028
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/19/2023 10/19/2026
Leak Detect - Piping Sump Sensor 7/31/2025 7/31/2026
Spill Contain Device Single Wall Spill Bucket 10/19/2023 10/19/2026
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/24/2002 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 7/31/2002 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/31/2002

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/31/2025 7/31/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 7/31/2025 7/31/2026
Overfill Prev Device Overfill Drop Tube Valve 7/31/2025 7/31/2028
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 10/19/2023 10/19/2026
Leak Detect - Piping Sump Sensor 7/31/2025 7/31/2026
Spill Contain Device Double Wall Spill Bucket 7/24/2024 7/24/2027
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found