Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3038392
Status: Active
Facility Name: Maquon Miracle Mart
Address: 319 Main Street Maquon, IL 61458
County: Knox
Property Parcel: 19-04-211-013
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000383
Green Tag Issue Date: 4/25/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Mihir Properties, LLC
Owner Address: 319 Main Street Maquon, IL 61458
Owner Status: Current Owner
Purchase Date: 12/27/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/23/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041095 Mihir Properties, LLC Current Owner 12/27/2023
U0034895 GBL Properties, Inc. Former Owner 5/27/2021
U0032925 Village of Maquon Former Owner / Operator
U0028180 Knox County Rural Improvement Foundation Former Owner / Operator

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00517-2026UPG Upgrade Approved / Issued 5/6/2026 5/6/2026 11/6/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020260779 (Pending)    Issue Date: 3/23/2026    Expiration Date: 5/22/2026    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Annual line precision and mechanical line leak detector functional test not completed.
1, 2 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use: Dispensing
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/10/1999 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 5/26/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/26/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c with CSLD 4/13/2026 4/13/2027
Overfill Prev Device Overfill Drop Tube Valve 4/13/2026 4/13/2029
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 4/13/2026 4/13/2029
Leak Detect - Piping Sump Sensor 4/13/2026 4/13/2027
Spill Contain Device Double Wall Spill Bucket 4/13/2026 4/13/2029
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 4/23/2026
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 3/27/2024



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/10/1999 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: 5/26/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/26/1999

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/23/2026 4/23/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c with CSLD 4/13/2026 4/13/2027
Overfill Prev Device Overfill Drop Tube Valve 5/13/2026 5/13/2029
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 4/13/2026 4/13/2029
Leak Detect - Piping Sump Sensor 4/13/2026 4/13/2027
Spill Contain Device Double Wall Spill Bucket 5/13/2026 5/13/2029
Tank Fiberglass Single Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Pisces Precision Test (Piping) Pass 4/23/2026
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 3/27/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms