Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3032054
Status: Active
Facility Name: Kwik Shop
Address: 118 W. Court Cambridge, IL 61238
County: Henry
Property Parcel: 18-07-404-021
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001603
Green Tag Issue Date: 10/18/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Karnal, Inc.
Owner Address: 118 W. Court Cambridge, IL 61238
Owner Status: Current Owner
Purchase Date: 4/29/2021
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 2/1/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/18/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040238 Karnal, Inc. Current Owner 4/29/2021
U0020533 Kwik Shop & Go Inc Former Owner 12/26/1987

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251769 (Pending)    Issue Date: 7/14/2025    Expiration Date: 9/12/2025    View NOV Form

Tanks Violations
Facility Fire Extinguishers - Past due for annual testing - Fuel Island Extinguisher

NOV Number: E0020251770 (Pending)    Issue Date: 7/14/2025    Expiration Date: 9/12/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Ground cover missing handle - repair or replace handle to allow for inspection.
2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Support for ground cover serverly damaged - repair or replace to allow for inspection.
1, 2 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Operations & Maintenance plan missing required frequencies - Paperwork on site not filled out
1, 2 Piping sacrificial anode system not tested (required every 3 years).
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2 Tank sacrificial anode system not tested (Required every 3 years).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8200 Gasoline - Regular Currently in use Federal $0.00
2 8200 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms

No Forms Found