| 5 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP - Conatinment ground cover deteriorated - collapsing inward and missing handles repair or replace to allow for inspection. |
| 5 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP- Containment support components missing - repair or replace |
| 6 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover missing handles repair or replace to allow for inspection. |
| 5 |
Miscellaneous - Line interstitial sensors submerged in liquid and not in alarm- repair or replace. |
| 6 |
Miscellaneous - Dispenser cover must be removable to allow for UDC inspection. |
| 6 |
Miscellaneous - Line interstitial sensors submerged in liquid and not in alarm- repair or replace. |
| 5, 6, 7 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
| 7 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - STP |
| 5, 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP's |