Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3014834
Status: Active
Facility Name: Gas N Dash Mart
Address: 809 19th Street East Moline, IL 61244
County: Rock Island
Property Parcel: 09-30-116-027
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000360
Green Tag Issue Date: 2/29/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Parm & Preet, Inc.
Owner Address: 404 East College Street Unite 1206 Iowa City, IA 52240
Owner Status: Current Owner
Purchase Date: 11/2/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 8/13/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033914 Parm & Preet, Inc. Current Owner 11/2/2006
U0029267 M C Petroleum LLC Former Owner 1/1/2000
U0027813 Samules Jr Wilbert L Former Owner 10/1/1998
U0012898 Robin Hood Stores Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261313 (Pending)    Issue Date: 5/15/2026    Expiration Date: 7/14/2026    View NOV Form

Tanks Violations
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Spill bucket support components deteriorated
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Transition ground cover missing handles- repair or replace handles to allow for inspection.
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - ATG ground cover support components missing.
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - STP ground cover deteriorated repair or replace. Also missing handles to allow for inspection.
3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Transition sump testing past due 11/3/2025

NOV Number: E0020261319 (Pending)    Issue Date: 5/15/2026    Expiration Date: 7/14/2026    View NOV Form

Tanks Violations
1, 3 Impressed current system failed test or appears non operational. Must repair. - Impressed current system appears non operational - must repair.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
07-0139 4/30/2007 Abandonment Log 00429-2007ABN

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
07-0139 Ineligible 3/23/2009 4/9/2009 $Not Selected
07-0139 Eligible 3/11/2010 4/23/2010 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 43 Abandoned Date:
Install Date: 1/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1983

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 9/29/2025 9/29/2026
Corrosion Prot - Tank Impressed Current Cathodic Protection 9/29/2025 9/29/2026
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/29/2025 9/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c with CSLD 9/29/2025 9/29/2026
Overfill Prev Device Overfill Drop Tube Valve 9/29/2025 9/29/2028
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 9/29/2025 9/29/2028
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 9/29/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/18/1986 Abandoned Material: Inert material mixed with portland cement
Current Age: 43 Abandoned Date: 4/30/2007
Install Date: 1/1/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1983

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Tank Lining Materials Internal

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/18/2007 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 4/27/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/27/2007

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 9/29/2025 9/29/2026
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/29/2025 9/29/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c with CSLD 9/29/2025 9/29/2026
Overfill Prev Device Overfill Drop Tube Valve 9/29/2025 9/29/2028
Piping Flexible Double Wall A.P.T. Poly Tech XP 1500 N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Piping Single Wall Transition Sump 11/30/2022 11/30/2025
Leak Detect - Piping Sump Sensor 9/29/2025 9/29/2026
Spill Contain Device Single Wall Spill Bucket 9/29/2025 9/29/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech XP 1500 Precision Test (Piping) Pass 8/4/2020
Piping Steel Single Wall Piping Precision Test (Piping) Pass 9/29/2025
Tank Fiberglass Single Wall XERXES Precision Test (Tank) Pass 1/24/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms