Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3013034
Status: Active
Facility Name: Jaswal, Inc.
Address: 301 North Canal Street Annawan, IL 61234
County: Henry
Property Parcel: 15-03-200-008
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000355
Green Tag Issue Date: 2/14/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: Jaswal Properties, Inc.
Owner Address: 301 North Canal Street Annawan, IL 612344824
Owner Status: Current Owner
Purchase Date: 6/6/2006
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/1/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033515 Jaswal Properties, Inc. Current Owner 6/6/2006
U0001282 Beck Oil Company of Illinois Former Owner 8/8/2002
U0009195 Lindburg Oil Former Owner 9/16/1981

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020261411 (Pending)    Issue Date: 6/1/2026    Expiration Date: 7/31/2026    View NOV Form

Tanks Violations
Facility Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters

NOV Number: E0020261415 (Pending)    Issue Date: 6/1/2026    Expiration Date: 7/31/2026    View NOV Form

Tanks Violations
8 Dispensers - hoses cracked, split or worn and require replacement
8 Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection)
Facility Electrical Does Not Comply - DSL ATG riser has open electrical
6, 7, 8 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Transition sump with sensor

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
07-1386 10/16/2007 Removal Log 01441-2007REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
02-1185 Eligible 1/17/2003 1/31/2003 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/16/2007
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/16/2007
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1967 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/16/2007
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1967 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/16/2007
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 1/1/1972 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1972

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 500 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 7/1/1992 Abandoned Material:
Current Age: 72 Abandoned Date:
Install Date: 1/1/1954 Red Tag Issue Date:
Last Used Date: 9/1/1973 Fee Due:
Product Date: 1/1/1954

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/26/2007 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 10/23/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2007

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2025 6/6/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1000 with SCALD 6/6/2025 6/6/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 6/6/2025 6/6/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Piping Single Wall Transition Sump 6/6/2025 6/6/2028
Leak Detect - Piping Sump Sensor 6/6/2025 6/6/2026
Spill Contain Device Single Wall Spill Bucket 6/6/2025 6/6/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/6/2025



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/26/2007 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 10/23/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2007

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2025 6/6/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1000 with SCALD 6/6/2025 6/6/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 6/6/2025 6/6/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2025 6/6/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/6/2025



Tank Number 8

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/26/2007 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 10/23/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2007

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2025 6/6/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1000 with SCALD 6/6/2025 6/6/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 6/6/2025 6/6/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Piping Single Wall Transition Sump 6/6/2025 6/6/2028
Leak Detect - Piping Sump Sensor 6/6/2025 6/6/2026
Spill Contain Device Single Wall Spill Bucket 6/6/2025 6/6/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/6/2025



Tank Number 9

Capacity: 2000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/26/2007 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 10/23/2007 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/23/2007

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/6/2025 6/6/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1000 with SCALD 6/6/2025 6/6/2026
Overfill Prev Device Ball Float Vent Valve EBW 308 6/6/2025 6/6/2028
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2025 6/6/2028
Tank Fiberglass Single Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test (Piping) Pass 6/6/2025

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found